A
Air damper setting (A).
To act on the screw in figure:
• to increase output,
turn screwdriver clockwise
• to reduce output,
turn screwdriver counterclockwise
!
Risk of air blast!
Continuously check CO, CO 2 and soot emissions when adjusting the output of
the burner. Optimise combustion values in the event of CO formation. CO must
not exceed 50 ppm.
Pre-setting diagrams in appendix
Before start-up adjust the burner
parameters according to the settings given
in the diagrams for GAS/LPG.
These values have been determined in
our test labs and are useful for the first
switch-on as final setting must be done
using a combustion analyzer.
How to read and adjust the values:
- determine the output required
- determine the combustion chamber back-
pressure
- read the position of the head in the
diagram and adjust it according
- read the position of the air flap and adjust
it according
12
www.ecoflam-burners.com
A
MAX GAS 40 P
Firing head setting (B).
To act on the screw in fi gure:
• turn Allen key till you reach the
requested value (index 0-4,5).
Optimising combustion values
The factory setting shall be modified
according to the output requeired.
The diagrams of air/head setting
that are available in the appendix
of this manual are a guide for ensuring
that the burner functions as well as
possible.
output (kW)
B
MAX GAS 70-120 P
B
Adjustment of gas solenoid valve
Refer to the gas train manual for the gas
setting of the gas train selected.
Note: observe the minimum required
flue gas temperature specified by the
boiler manufacturer and the
requirements demanded of flue gas
ducts for avoiding condensation.
MAX GAS 40 P
MAX GAS 70-120 P
head gas pressure (on elbow) (mbar)
head position
air damper position