NOTE: The bottom of the unit
should
be
higher than the ceiling board.
Generally,
L
following figure) should be half the
length of the suspension bolt or
long enough to prevent the nuts
from coming off.
CAUTION
Ensure that the unit is completely
level.
Improper
cause the drain pipe to back up into
the unit or water leakage.
NOTE: Ensure that the indoor unit is
level. The unit is equipped with a
built-in drain pump and float switch.
If the unit is tilted against the direc-
tion of condensate flows (the drain-
pipe side is raised), the float switch
may malfunction and cause water to
leak (for some models)
Water level
10-25mm(0.4-0.98")
(indicated
in
installation
NOTE FOR NEW HOME INSTALLATION
When installing the unit in a new
home, the ceiling hooks can be
embedded in advance. Make sure
that the hooks do not come loose
the
due to concrete shrinkage. After
installing the indoor unit, fasten the
installation paper template onto the
unit with bolts to determine in
advance the dimension and position
of the opening on the ceiling. Follow
the
instructions
remainder of the installation.
can
Step 3: Drill wall hole for connective piping
1. Determine the location of the wall
hole based on the location of the out-
door unit.
2.
Using a 65mm (2.56") or 90mm
(3.54") (depending on models) core
drill, drill a hole in the wall. Make
sure that the hole is drilled at a
slight downward angle, so that the
outdoor end of the hole is lower
than the indoor end by about 12mm
(0.5"). This will ensure proper water
drainage.
3. Place the protective wall cuff in the
hole. This protects the edges of the
hole and will help seal it when you
finish the installation process.
above
for
the
Paper pattern
for installation
(on some
models)
Center of the
ceiling openiing
bolts
V.3