Note on Adding Refrigerant

Some systems require additional charging depending on pipe lengths. The
standard pipe length varies according to local regulations. For example, in
North America, the standard pipe length is 7.5m (25'). In other areas, the
standard pipe length is 5m (16'). The refrigerant should be charged from the
service port on the outdoor unit's low pressure valve. The additional refrigerant
to be charged can be calculated using the following formula:
R410A:
(orifice tube in the indoor
unit):
R410A:
(orifice tube in the outdoor
unit):
R32 :
CAUTION:
φ6.35 (1/4")
(Total pipe length
- standard pipe
length) x 30g
(0.32oZ) /m(ft)
(Total pipe length
- standard pipe
length) x 15g
(0.16oZ) / m(ft)
(Total pipe length
- standard pipe
length)x 12g
(0.13oZ) / m(ft)
mix refrigerant types.
DO NOT
Liquid Side Diameter
φ9.52 (3/8")
(Total pipe length
- standard pipe
length) x 65g
(0.69oZ) /m(ft)
(Total pipe length
- standard pipe
length) x 30g
(0.32oZ) /m(ft)
(Total pipe length
- standard pipe
length)x 24g
(0.26oZ)/m(ft)
φ12.7 (1/2")
(Total pipe length
- standard pipe
length) x 115g
(1.23oZ) /m(ft)
(Total pipe length
- standard pipe
length) x 65g
(0.69oZ) / m(ft)
(Total pipe length
- standard pipe
length)x 40g
(0.42oZ)/m(ft)