Descargar Imprimir esta página

Riello FS10 Instrucciones De Instalación, Uso Y Mantenimiento página 7

Publicidad

Idiomas disponibles

Idiomas disponibles

3.4
ELECTRICAL WIRING
3.4.1 STANDARD ELECTRICAL WIRING
Ionization probe
Electrode
Ignition transformer
Air pressure switch
Motor
Blue
White
Black
NOTES:
– Do not exchange the neutral with the phase and
connect exactly the above wiring.
– Wires of min. 1 mm
standards and legislation).
– Carry out a safe earth connection.
– Verify that the burner stops by operating the boiler control thermostats
and that the burner locks out by separating the red ionisation probe lead
connector.
– The electric wiring carried out by the installer must be in compliance
with regulations in force in the Country.
2824
Connector
Control box
RMG 88.620A2
D4275
2
section. (Unless requested otherwise by local
~
230V
50Hz
5
GB
Burner earth
Suppressor
CARRIED-OUT
BY THE INSTALLER
ATTENTION
In the case of phase-phase
feed, a bridge must be fit-
ted on the control box ter-
minal
board
between
terminal 6 and the earth
terminal.
LEGEND
XP6 – 6 pole socket
XP7 – 7 pole socket
X6 – 6 pin plug
X7 – 7 pin plug
B4 – Working signal
h1 – Hour counter
PG – Minimum gas pressure
switch
S3 – Remote lock-out signal
(230V - 0.5 A max.)
T6A – Fuse
TL – Limit thermostat
TS – Safety thermostat
V10 – Safety valve
V11 – Adjustment valve

Publicidad

loading

Este manual también es adecuado para:

3756433