A
Contact NO (Normally Open) to start and stop the generator:
• Contact open: generator on standby
• Contact closed: generator starts and stays running until the contact
reopens.
Please note that not all solar controllers are prepared to work with a generator.
Check with your solar technician or with the supplier of the controller.
Start sequence: When the generator contact closes, the start attempt begins. If
this is unsuccessful, new attempts will be performed up to a maximum of five. If
the generator fails the five pre-programmed attempts, it will fall into error mode.
B
Generator battery support: The generator has a charging port on the panel to
recharge or to keep the battery charge. Connect the charger supplied to the 230V
mains socket and its DC 14V output to the port on the control panel.
NOTE: Do not use a charger different of the original. If you have to replace the
original charger, purchase an original GENERGY.
C
Use the 32A socket as power supply for the controller: This 32A socket
allows the maximum power output from the generator.
NOTE: Do not use one of the two 16A sockets for this purpose because the
power output will be limited to 16A (3680W).
About fuel:
NOTE:
Make sure that the generator starts at least every two months.
Otherwise perform a manual start and keep the generator running for a few
minutes to ensure that the fuel in admission circuit lines is renewed.
NOTE: If the generator is not used, or if is used very few times, make sure that
the same gasoline does not remain in the tank for more than a year, otherwise
replace it.
NOTE:
If you are aware that the generator will not run for long periods,
choose to fill the tank completely. In contact with oxygen, the gasoline accelerates
its degradation. If the tank is completely full the degradation will be slower. You
can also add a gasoline stabilizer to delay the degradation.
NOTE: Never, GENERGY will be responsible for personal or property damage
that may arise from the lack of supply due to a generator failure.
If you have any questions, contact us by spv@sg-group.es .
69