Final tests
After installation, make sure everything is working with an overall system test.
SB250-N and SB2100-N barriers
Movement control in the cell: intrusion alarm.
Extended interruption of the cell for more than 1 minute: disqualification
alarm.
For SB4200-N barriers
Movement control in only one of the two cells: alarm not triggered.
Movement control in both of two cells: intrusion alarm.
Extended interruption of both cells for more than 1 minute: disqualification
alarm.
For SB450-N and SB4100-N barriers
"AND" mode:
Movement control in only one of the two cells: alarm not triggered.
Movement control in both of two cells: intrusion alarm.
Extended interruption of both cells for more than 1 minute: disqualification
alarm.
"OR" mode:
Movement control on the top cell: intrusion alarm.
Movement control in the lower cell: intrusion alarm.
Extended interruption of one of the two cells for more than 1 min:
disqualification alarm.
Modules installed in columns
Simple detection:
Movement control in only one of the two cells: intrusion alarm.
Extended interruption of one cell for more than 1 min: disqualification alarm.
Interdetection:
Movement control in only one of the two cells: alarm not triggered.
Movement control in both of two adjacent cells: intrusion alarm.
Movement test on two adjacent cells on two different modules (except
SB4200-N): intrusion alarm.
Extended interruption of one of two cells for more than 1 min: disqualification
alarm.
If the bottom cell is enabled: Movement control in the bottom cell for more
than 1.5 s: intrusion alarm.
28
SB Series AIR Beam Detectors Installation Manual