Descargar Imprimir esta página

L.B.White Sentry ST060 Manual Del Usuario E Instrucciones página 14

Calentadores de tubo radiante

Publicidad

Idiomas disponibles

Idiomas disponibles

14
Sentry Tube Heaters
Air Turbulation Strips
& Exhaust Vent
When installing the air turbulators, make
sure that the strips fit into the tube and
do not extend beyond the end of the
tube. See FIG. 9a.
FIG. 9a
TURBULATION STRIPS
REGARDLESS OF TUBE DESIGN:
-- Ensure the green clip is installed on the exhaust vent.
See Fig. 9b.
-- Insert the exhaust vent to the end of the last tube.
-- Push the exhaust vent until the tube is stopped at
the rivet.
FIG. 9b
GREEN
CLIP
Owner's Manual • Sentry
INSERT STRIP ASSEMBLY
INTO LAST 10 FT. OF TUBE
OUTLET END
30 FT.
40 FT.
4
3
Sediment Trap Assembly
Assemble the tee, nipple, and cap to the nipple at
the gas inlet of heater. See Fig. 10. Use a wrench to
hold the pipe nipple when installing the sediment trap.
Tighten securely. The sediment trap assembly must
always be mounted in a vertical position. Check all
connections for gas leaks using approved gas leak
detectors.
FIG. 10
NIPPLE
TO GAS CONTROL VALVE INLET
C
Manual Shut-off Valve,
Hose & Regulator
1. Assemble the components together. See Fig. 11.
This view shows general assembly of the
components. The regulator must always be
mounted so its vent, regardless of location on the
regulator, is always pointed downward. Ensure
hose is positioned away from the heater.
2. Tighten all connections securely and check
for gas leaks
FIG. 11
REGULATOR VENT
TO CONTROL
VALVE INLET
TEE
NIPPLE
CAP
REGULATOR
NIPPLE
VALVE, MANUAL
SHUT-OFF
GAS HOSE
ADAPTER
SEDIMENT TRAP

Publicidad

loading

Este manual también es adecuado para:

Sentry st080Sentry st100Sentry st125