6.1.2
Control buttons
PUSHBUTTONS
DISPLAY
Vent. Activa ON
Active Vent. OFF
Paro Zumbador
Stop Buzzer
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS– FIRE PROTECTION MANUFACTURER
34
C/ Compositor Wagner, 8 – P.I. Can Jardí - 08191 RUBÍ (Barcelona) ESPAÑA.
COsensor Control Panel
MCO120 / MCO120DVB
► During the configuration of the delayed activation, pressing it
1
increases the time by 1 minute.
► During setting the level on/off, pressing it increases the level by
10 ppm.
The button is associated with the configuration of the control panel
by means of command button 3.
2
► During the configuration of the delayed activation, pressing it
decreases the time by 1 minute.
► During setting the level on/off, pressing it decreases the level
by 10 ppm.
Allows the panel control setting.
► 1 pulsation: Ventilation 1 activation level (CO in ppm).
► 2 pulsations: Delay activation of ventilation 1 (in min).
► 3 pulsations: Ventilation 2 activation level (CO in ppm, only
3
DVB model).
► 4 pulsations: Delay activation of ventilation 2 (in min, only DVB
model).
► 5 pulsations: Alarm activation level (CO in ppm).
► 6 pulsations: Delay activation of alarm (in min).
Activate/deactivate the ventilations
4
The model DVB activates and deactivates both ventilation systems
at the same time.
Stop buzzer.
5
It allows to stop the buzzer until a new event occurs (alarm or
fault).
Table 5: Front panel pushbuttons description
FABRICANTE DE PRODUTOS CONTRA INCÊNDIOS
Tlf.: +34 935 862 690 - cofem@cofem.com -
DESCRIPTION
www.cofem.com