Sagi ME70LTR Manual De Uso E Instalación página 138

Cabinas frigorificas
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 157
C6
0
200
C7
0
200
C8
0
15
C10
0
9999
LABEL
MIN.
MAS.
d0
0
99
d1
0
2
d2
-99
99
d3
0
99
d4
0
1
d5
0
99
d6
0
2
d7
0
15
d8
0
3
d9
-99
99
d11
0
1
d15
0
99
d16
0
99
d18
0
999
d19
0
40
d20
0
999
d21
0
500
d22
0
19,9
LABEL
MIN.
MAS.
A1
0
99
A4
0
99
A6
0
99
A7
0
240
A8
0
240
A9
0
240
A11
0,1
15
LABEL
MIN.
MAS.
F0
0
4
condenser temperature is higher than that at which the condenser overheating alarm is activated (code
°C/°F (1)
"COH") (7)
condenser temperature above which the compressor shut down alarm is activated (code "CSd")
°C/°F (1)
compressor shut down alarm delay (code "CSd") (8)
min
number of compressor operation hours above which the request for maintenance is triggered
h
0 = the request shall never be tri
U.M.
DEFROST
if d8 = 0, 1 or 2, defrost interval
h
0 = interval defrost will never be activated
if d8 = 3, maximum defrost interval
type of defrost
0 = ELECTRIC - during defrost the compressor will remain off and the defrost output will be activated;
evaporator fan activity will depend on F2 parameter
-
1 = BY HOT GAS - during defrost the compressor will be switched on and the defrost output will be
activated; evaporator fan activity will depend on F2 parameter
2 = VIA STOPPING OF COMPRESSOR - during defrost the compressor will remain switched off and
the defrost output will remain deactivated; evaporator fan activity will depend on F2 parameter
°C/°F (1)
evaporator temperature at end of defrost; see also d3
if P3 = 0 or 2, defrost duration
min
if P3 = 1, maximum defrost duration; see also d2
0 = defrost will not be activated
defrost when device is switched on (5)
-
1 = YES
if d4 = 0, minimum time between switching on of device and activation of defrost (5)
min
if d4 = 1, delay in activation of defrost after device is switched on (5)
magnitude displayed during defrost (only if P5 = 0)
0 = room temperature or CPT temperature
1 = if on activation of defrost, the room temperature or CPT temperature is below the "work setpoint + +
Δt", at maximum " work setpoint + Δt"; if on activation of defrost, the room temperature or CPT
-
temperature is above "work setpoint + Δt", at maximum the room temperature or CPT temperature on
activation of defrost (9) (10)
2 = label "dEF"
dripping duration (during dripping the compressor will remain switched off and the defrost output will
remain deactivated; if d16 = 0, evaporator fan activity will depend on F2 parameter); if d16 ≠ 0, the
min
evaporator fan shall remain off)
defrost activation methods
0 = AT INTERVALS - FOR TIME - defrost will be activated once the device has altogether been
running for time d0
1 = AT INTERVALS - FOR COMPRESSOR SWITCH-ON - defrost will be activated once the
compressor has altogether been switched on for time d0
-
2 = AT INTERVALS - FOR EVAPORATOR TEMPERATURE - defrost will be activated when the
evaporator temperature has remained below the temperature d9 for a total time of d0 (11)
3 = ADAPTIVE - defrost will be activated at intervals, whose duration will each time depend on the
duration of compressor switch-ons, the evaporator temperature and the door switch input activation;
see also d18, d19, d20, d22, i13 and i14 (11)
°C/°F (1)
evaporator temperature is higher than that at which the defrost interval counter is suspended (only if d8 = 2)
defrost alarm switches off once maximum time limit has been reached (code "dFd"; only if P3 = 1 and
in absence of evaporator probe error (code "Pr2")
-
1 = YES
minimum time that the compressor must be switched on before defrost can be activated (only if d1 = 1)
min
(12)
pre-dripping duration (during dripping the compressor will remain switched off, the defrost output will
min
be activated and the evaporator fan shall remain off)
defrost interval (defrost will be activated when the compressor has been on totally, with the evaporator
min
temperature below that of d22, for time d18; only if d8 = 3)
0 = defrost will never be activated due to the effect of this condition
evaporator temperature below which the defrost is activated (relative to the evaporator temperatures
°C/°F (1)
average, or "evaporator temperatures average - d19"; only if d8 = 3)
minimum consecutive time the compressor must be switched on such as to provoke the defrost
min
activation
0 = defrost will never be activated due to the effect of this condition
minimum duration of compressor continuous operation from the switching on of the device (provided
that the "cell temperature – working setpoint" or "CPT temperature - working setpoint" difference
min
exceeds 10 °C/20 °F) and from the activation of the "rapid cooling" function so as to start the defrost
0 = defrost shall never be activated as a consequence of this condition
evaporator temperature above which the defrost interval count shall be suspended (relating to the
average of evaporator temperatures, that is to say, "evaporator temperatures average + d22"; only if
°C/°F (1)
d8 = 3); see also d18
U.M.
TEMPERATURE ALARMS
room temperature or CPT temperature below which the minimum temperature alarm is triggered (code
°C/°F (1)
"AL"; it concerns the working setpoint, that is to say, "working setpoint - A1"); see also A11
0 = alarm absent
room temperature or CPT temperature above which the maximum temperature alarm is triggered
(code "AH"; it concerns the working setpoint, that is to say, "working setpoint + A4"); see also A11
°C/°F (1)
0 = alarm absent
delay in maximum temperature alarm (code "AH") after the device is switched on (5)
10 min
min
minimum temperature alarm delay (code "AL") and maximum temperature alarm delay (code "AH")
delay in maximum temperature alarm (code "AH") from the conclusion of evaporator fan standstill (13)
min
delay in maximum temperature alarm (code "AH") following the deactivation of the door switch input (14)
min
°C/°F (1)
differential of A1 and A4 parameters
U.M.
EVAPORATOR FAN AND CONDENSATOR FAN
evaporator fan activity during normal operation
-
0 = switched off
20