• For saving displayed measurement result press the "SAVE" function
(12) twice, for further instructions see the "Memorizing example"
section.
• By setting the test current to 20 A, the loop impedance measurement will
be executed quickly and accurately. Potential motor protection switch or
residual current device (RCD) can be triggered during the measurement,
because of high test current.
• By setting the test current to LOW, low test current is used, and the
motor protection switch or RCD will not be triggered during the
measurement. However, the measurement takes more time and the
measurement range as well as resolution are reduced.
21
key