Jet Swim Athlete
Electrical installation
The pump engine must be switched on via the Jet Swim automatic cabinet, see wiring diagram below.
Check the nameplate of the pump engine for proper connection on coupling plates.
NOTE! The pump must never be started without being filled with water.
WARNING
• The electrical installation may only be carried out by a qualified electrician in accordance
with the instructions provided with the pump.
• As electrical installation regulations differ from country to country, contactors, cables,
connection components, and enclosures must be selected based on local regulations.
• A main isolator must be installed before all live electrical connections on the pump.
This must be an all-pole isolator that satisfies the requirements set out in IEC/EN 60335-1
paragraphs 7.12.2, 22.2 and 24.3.
• The pump shall be fed via a residual current device with maximum leakage current of no
more than 30mA.
• The pump shall be fitted with an all-pole switch and approved automatic motor circuit
breaker that should be set to match the motor's rated current, see the pump motor rating
plate.
• Check that the pump's direction of rotation is the same as system flow – see the arrow
on the motor housing.