INTRODUCTION
Gate Access
Disconnect power BEFORE making electrical connections. Below is an example of a wiring setup for gate access. Gate access can be
wired to Door 1 or 2.
INTRODUCTION
NOTE: Power Supplies shall be UL Listed Commercial 294 or 603 power limited output Power Supplies.
RFID ANTENNA
NOTE: Power supply for
RFID antenna is not provided.
DO NOT use the power supply
for the door controller.
AUXILIARY RELAY
Model MG1300
For AC Power:
Install a Siemens S10K30MOV
(Metal Oxide Varistor) (provided) or equivalent
Use 18-22 AWG
-
For DC Power:
Install a 1N4005 diode
or equivalent
PRIMARY RELAY
GATE OPERATOR
PRE-INSTALL
WIRING
PRE-INSTALL
WIRING
WIEGAND
OR
NORMALLY CLOSED
+
COMMON
Power for Maglock
(Not Provided) DO
NOT use the power
supply for the
controller
OPEN
Common
(Exit Input)
NETWORK
NETWORK
KEYPAD
OR
NOTE: For KPR2000 keypad
wire the pink and black (ground)
wires together.
REQUEST TO EXIT
EXTERNAL FREE EXIT
LOOP DETECTOR
NC
NC
COM
COM
NO
NC
COM
COM
NO
NO
NC
COM
NO
NC
COM
NO
15
ACCESS CONTROL
ACCESS CONTROL
NOTES:
• The length of the unshielded
wires should be kept to a minimum
to avoid electrical noise.
• When extending the reader connection,
the shield wire must be connected to an
READER
earth ground bus, but should NEVER be
connected at the reader.
PUSH
BUTTON
OR
INSTALL
INSTALL