Vaillant sensoHOME VRT 380f/2 Manual De Uso E Instalación página 10

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 53
MENU → CONTROL
→ Mode:
→ Name of zone
→ Absence
→ DHW
→ Mode:
→ Hot water boost
→ Ventilation boost
→ Time programme
assistant
→ Installation off
10
Weekly planner: Up to 12 time periods and desired temperatures can
be set per day
The competent person sets how the heating installation behaves out-
side of the time period in the Set-back mode: function.
In Set-back mode: means:
– Eco: The heating is switched off outside of the time periods. Frost
protection is activated.
– Normal: The set-back temperature applies outside of the time peri-
ods.
Desired temperature: °C: Applies within the time periods
Factory setting: Set-back temperature: °C 15 °C
→ Off
Heating is switched off, domestic hot water continues to be available,
frost protection is activated
Changing the name Zone 1, which was set at the factory
→ All: Applies only to any zones within the specified time period
→ Zone: Applies for the selected zone in the specified time period
During this time, heating mode runs at the defined set-back temperat-
ure. Domestic hot water mode and circulation are switched off.
Factory setting: Set-back temperature: °C 15 °C
→ Manual
Uninterrupted retention of the domestic hot water temperature
→ Time-contr.
Domestic hot water weekly planner: Up to three time periods can be
set per day
DHW temperature: °C: Applies within the time periods
Domestic hot water mode is switched off outside of the time periods
Circulation weekly planner: Up to three time periods can be set per
day
The circulation pump pumps hot water to the draw-off points within the
time periods
Outside of the time periods, the circulation pump is switched off
→ Off
Domestic hot water mode is switched off
Heating up the water in the cylinder once
Heating mode is switched off for 30 minutes.
Programming of the desired temperature for Monday–Friday and Sat-
urday–Sunday; the programming applies for the time-controlled Heat-
ing, DHW and Circulation functions.
Overwrites the weekly planner for the Heating, DHW and Circulation
functions.
Installation is switched off. Frost protection remains active.
Operating and installation instructions 0020323648_01
→ DHW temperature: °C
→ Domestic hot water weekly planner
→ DHW temperature: °C
→ Circulation weekly planner