MENU → SETTINGS → Installer level → Installation configuration
The behaviour can be adjusted separately for each heating circuit.
→ Room temp. mod.:
The installed temperature sensor measures the current room temperature. The control calcu-
lates a new target room temperature that is used to adjust the flow temperature.
– Difference = Set target room temperature - current room temperature
– New target room temperature = Set target room temperature + difference
Prerequisite: The control is assigned to the zone in which the control is installed in the Zone
assignment: function.
The Room temp. mod.: function is ineffective if No assignmt is activated in the Zone as-
signment: function.
→ Zone
14
→ Eco
The heating function is switched off and the
frost protection function is activated.
At outdoor temperatures that are below
4 °C for longer than four hours, the control
switches the heat generator on and regulates
to the Set-back temperature: °C. At an
outdoor temperature above 4 °C, the control
switches the heat generator off. The monit-
oring of the outdoor temperature remains
active.
Heating circuit behaviour outside of the time
periods. Prerequisite:
– Time-contr. is activated in the Heating →
Mode: function.
– Active or Inactive is activated in the
Room temp. mod.: function.
If Expanded is activated in the Room temp.
mod.:, the control regulates to the target
room temperature 5 °C independently of the
outdoor temperature.
→ Normal
The heating function is switched on. The con-
trol regulates to the Set-back temperature:
°C.
Prerequisite:
– Time-contr. is activated in the Heating →
Mode: function.
→ Inactive
→ Active
Adjusting the flow temperature based on the
current room temperature.
→ Expan-
Adjusting the flow temperature based on the
ded
current room temperature. The control also
activates/deactivates the zone.
– The zone is deactivated: Current room
temperature + 2/16 K > set room temper-
ature
– Zone is activated: Current room temperat-
ure < set room temperature - 3/16 K
Operating and installation instructions 0020323648_01