1. In the basic menu use the cursor keys or to select Other selections.
Short selection
Free selection
Other selections
ENTER‐OK
2. Press
ENTER
to confirm.
3. Use the cursor key to select Service.
Refrigerant Test
Hybrid service
Service.
ENTER‐OK STOP‐EXIT
4. Press
ENTER
to confirm.
5. Enter the password
2688
6. Use the cursor keys to activate any fields you need (dark fields are activated).
Oil bottle
150ml
250ml
UV bottle
150ml
250ml
7. Press
ENTER
to confirm.
8. Press
STOP
to access the standby menu..
12.12 Filling up the internal refrigerant container
When the A/C service unit is started for the first time, the A/C service unit displays Error 12, because the inter
nal refrigerant vessel must be filled from an external refrigerant vessel with at least 2000 g of refrigerant.
1. Press
STOP
to confirm.
The current supply quantities are displayed in the standby menu.
2. Connect the external refrigerant vessel to the A/C service unit.
Note Observe the instructions on the refrigerant vessels. Vessels for the R1234yf refrigerant have a
lefthand thread.
There are three different types of refrigerant vessel available:
• Refrigerant vessels without rising pipe: These refrigerant vessels have one connection. When filling the A/C
service unit, the connection must be on the bottom (turn the vessel upside down).
• Refrigerant vessels with rising pipe: These refrigerant vessels have one connection. When filling the A/C ser
vice unit, the connection must be at the top (place the vessel upright).
.
500ml
500ml