GLX-1 / TLX-1
Structural Rough-Ins – GLX & TLX
Mounting for Standard ADA and TAS height shown.
Areas highlighted in gray require sufficient backing
compliant with local building codes.
¾" (19)
Mounting Bracket
CODE
A
Install (1) ³⁄₈" wall anchor with a minimum pull-out force of 1,000 lb per local codes at locations shown
B
Install (2) wall anchors per bracket with a minimum pull-out force of 100 lb per local codes at locations shown
C
RIM
HEIGHT
34"
31"
26"
12
Wall Bracket
A
34"
(864)
31¼"
(794)
30½"
Bottom of Wall
(775)
Bracket to
Finished Floor
Access Panel
Provide structural backing compliant with local building codes.
VERTICAL HEIGHT
ADJUSTMENTS
No Adjustment
*Subtract 3"
*Subtract 8"
1/21/2021
C
L
10" (254)
A
B
(407)
8¼"
(210)
Finished Floor
C
DESCRIPTION
FIXTURE
STYLE
Standard ADA & TAS
At least one basin must meet dimensional
requirements and have proper reach, knee,
and toe clearance.
Juvenile ADA & TAS
At least one basin must meet dimensional
requirements and have proper reach, knee,
and toe clearance.
Junior
For use by younger children where ADA
guidelines are not a concern.
Secure bracket to wall using min. (2) ³⁄₈"
anchor bolts to the left of C/L and min. (2)
³⁄₈" anchor bolts to the right of C/L. The (2)
anchor bolts to the right of C/L must be
min. 16" apart from the anchor bolts to the
left of C/L. When mounting is complete,
check to ensure the bracket is level.
31½"
(801)
Bracket Slots
to Finished
Floor
16"
NOTES
Bradley • 215-1900 Rev. C: ECO 20-08-028B