5.4.7 Wiring analog inputs AI
NOTICE
Damage to the device and sensors!
Incorrectly connected and configured analog inputs/outputs may result in
damage to the device and sensor.
You can connect the following types of analog sensors:
In order to correctly record the analog signals, you must place the cable shield-
ing on the grounding bar. The cable shielding should only be removed just prior
to connecting to ensure that the section with unshielded cables is kept as short
as possible. The shielding must be connected with shielding clips.
Block diagram and wiring versions
Figure 36: Block diagram for analog inputs
1. Lead the wires into the connector and fasten them using a screwdriver.
2. Insert the plug into the respective slot in accordance with the connection dia-
5.4.8 Wiring DI 16-110 V digital inputs
If the device has DI 16-110 V connections, these have to be supplied with an
auxiliary voltage of 110 V DC.
i
1. Feed the wires into the terminal of the DI 16-110V plug in accordance with
2. Plug the connector into the respective slot and screw it into place.
Auxiliary power supply for digital inputs
1. Feed the wires into the terminals X8:2 and X8:1 of the X8 plug in accordance
2. Plug the connector into the respective slot and screw it into place.
Follow information about connecting analog sensors.
Configure analog inputs and outputs according to the connected sensors.
0/4...20 mA
0 to 10 V
PT100/PT1000 (2-wire, 3-wire, 4-wire) indirectly via measuring transducer
AI 4
D
A
Connection of a 2-
conductor measuring
transducer with current
output
gram [►Section 8.14, Page 59] and screw into place.
Check which version you have by looking at the connection terminal desig-
nation on the rear of the device.
the connection diagram [►Section 8.14, Page 59] and fasten them using a
screwdriver.
with the connection diagram [►Section 8.14, Page 59] and fasten them us-
ing a screwdriver.
CAN bus
Controller
Reinforced insulation
D
D
A
A
Connection of a 3-
Connection of a 4-
conductor measuring
conductor measuring
transducer with current
transducer with voltage
output
output
7820658/06 EN Mounting  
D
A
Connection of a 4-
conductor measuring
transducer with current
output
37