CAUTION
Electric shock!
The outputs of the DO assembly have plug-based electrical isolation. A mix-
ture of voltage ranges (e.g. extra low voltage and low voltage) or various
phases within a plug can lower the protection against electric shock.
Interface
Table 21: Connector X1 (group 0)
Interface
Table 22: Connector X2 (group 1)
Interface
Table 23: Connector X3 (group 2)
Interface
Table 24: Connector X4 (group 3)
Use the same voltage ranges within a plug.
Use the same phase within a plug.
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
Pin
Description
4
Common reference (common) output 1
3
Common reference (common) output 0
2
Output 1
1
Output 0
Pin
Description
4
Common reference (common) output 3
3
Common reference (common) output 2
2
Output 3
1
Output 2
Pin
Description
4
Common reference (common) output 5
3
Common reference (common) output 4
2
Output 5
1
Output 4
Pin
Description
4
Common reference (common) output 7
3
Common reference (common) output 6
2
Output 7
1
Output 6
7820658/06 EN Technical data  