Parameters
Setting range
Min / Max
Max. feed
20 – 90 °C
temperature
Min. feed
10 – 90 °C
temperature
Room Influ-
ence
Off,
0 K
1 – 20 K
Adjustment
-5 - +5 K
room sensor
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN
Description
The setting limits the feed temperature (measured at t
heating support function.
The determined target feed temperature of the HC is limited to the
maximum value set here.
If an optionally connected mixed HC requests a higher temperature of
the heat generator, this is taken into account. This means the internal
circulation pump of the heat generator always runs if the generator is
switched on. If the direct HC supplies the floor heating, a mechanical
temperature limiter must be installed to prevent any overheating of the
screed.
The determined target feed temperature of the HC is limited to the min-
imum value set here.
Only with the room control connected and assigned to the HC:
The setting of what influence the deviation of the room temperature
measured by EHS157034 from the current target value
4.2) has on the feed temperature.
Purely weather-compensated feed temperature control
Purely weather-compensated feed temperature control, but internal cir-
culation pump continues running until the next heating cycle after a
heat requirement during the setback cycle.
Causes a correction of the target feed temperature (parallel shift of the
heating curve) by the set factor. If the measured temperature lies 2 K
below the target value, the target feed temperature is increased by 2x
the set value.
Only with room control connected and assigned to the HC.
Individual adjustment of the room temperature relevant to the control
unit.
If a systematic deviation of the room temperature measured by the
EHS157034 to the actual temperature in the occupied area of this
room is determined, the measured value can be corrected by the set
value.
7
Parameter settings
Factory setting Increment Access
) with active
80 °C
V2
28 °C
Off
(see Chap.
0.0 K
BE HF
1 °C
N
E
1 °C
N
E
1 K
E
E
1 K
E
E
Operating Instructions
41