9.4
Messages
Messages are displayed using the LEDs on the control panel with the meanings
specified in the table. A precise description of the LEDs, 9.2 "Operator panel",
28. A detailed description of the error is available via the app.
LED
Function /
display
Auto
Button
LED lights up
Stop
Button
LED lights up
Display
Display
Service
Button
LED lights up
LED flashes
If errors exist, the error code is shown on the display.
ER
Alarm
Code
01
Minimum pressure
[1] Auto LED lights up
[5] Error LED lights up
[2] Pressure LED flashes
02.1
Low water
[1] Auto LED lights up
[5] Error LED lights up
[3.3] Level LED flashes
03
High water
[1] Auto LED lights up
[5] Error LED lights up
[3.1] Level LED lights up
05
Compressor run time
[1] Auto LED flashes
[4] Stop LED flashes
[5] Error LED flashes
[2] Pressure LED flashes
[3] Level LED off
06
Make-up time
[1] Auto LED lights up
[5] Error LED lights up
[3] Level LED flashes
07
Make-up cycles
[5] Error LED lights up
[4] Stop LED lights up
[3.3] Level LED lights up
08
Pressure measurement
[1] Auto LED off
[4] Stop LED flashes
[5] Error LED flashes
[2] Pressure LED flashes
Meaning
Start
Automatic operating mode
Maintenance / Interruption
Error
Display of pressure, level and
error code if a fault exists
Acknowledge / Start Self-
Service
Warning
Error
Causes
Set value p
not reached:
0
•
Compressor fault.
•
Air side leak of the system.
Too little water in the vessel (filling level <5%):
•
Make-up disabled.
•
Water loss in the system.
•
Filling level measurement defective.
Filling level >90%:
•
Make-up function defective (continuous
water supply)
•
External water entry through the system
(e.g. defective heat exchanger)
Maximum compressor run time exceeded:
•
Air side leak.
•
Compressor has no power.
Set max. make-up time has been exceeded:
•
Water loss in the system.
•
Automatic make-up not connected.
•
Make-up output insufficient.
•
Make-up hysteresis too high.
Number of set max. make-up cycles has been
exceeded:
•
Leakage in the system.
•
Controller receives incorrect signal.
Reflexomat RSC Smart — 08.01.2024-Rev. A
LED
Function /
display
Pressur
LED lights up
e
LED flashes
Level
LED lights up
in green
LED lights up
in yellow
LED flashes
yellow
Alarm causes can be eliminated by the operator or a specialist workshop. If this is
not possible, contact the Reflex Customer Service.
Note!
Elimination of the cause must be confirmed via the service button on the
control panel of the controller. All other alarms are automatically reset as
soon as the cause has been eliminated.
Remedy
•
Check the functioning of the compressor.
•
Check the sealing points for leak tightness.
•
If necessary, manually add water.
•
Check water level.
•
Check the make-up unit.
•
Check functioning of the "PV" solenoid valve.
•
Drain water from the vessel.
•
Check on-site heat exchanger for leakage.
•
Check the water loss and correct, if
necessary.
•
Seal any leak in the air system.
•
Check functioning of "PV" air side solenoid
valve.
•
Check functioning of compressor.
•
Check the set values.
•
Check automatic make-up.
•
Check water level.
•
Connect make-up line.
•
Seal any leakage in the system.
•
Check the set value.
•
If necessary, manually add water.
•
Check system for leakage.
•
Check the plug connection at the pressure
sensor.
•
Check functioning of the pressure sensor.
•
Compare the values from the app with the
pressure gauge
•
Check the cable for damage.
Controller
Meaning
Automatic operating mode
Fault (min. pressure, defective
pressure measurement,
deviation from set pressure,
etc.)
Automatic operating mode
Warning (make-up request,
high water)
Fault (low water, weight
measuring cell possibly
defective)
Alarm reset
-
-
-
"Service"
-
-
-
English — 29