Before to use this instrument the User Guide and Safety warnings must be
read and understood.
Safety procedures and rules for working near high voltage energized systems
must be observed during the use of this equipment. The generated voltages
and currents may be dangerous.
Before you begin the measurement verify the mains supply voltage
compatibility.
The micro-ohmmeter must be connected to earth point, through the green
terminal or the power cord (both use the same point).
During a circuit breaker measurement its contacts must be closed and
connected to an earth point. The end connected to an earth point must be
connected to the "C-" terminal.
Certified the measurement points in which will be connected all the terminals
are free of any voltage in relation to earth point and between each other. Take
in account that in a substation you will find in disconnected points high
potential levels in relation to the earth point. Those potentials are caused by
present electromagnetic fields and can be minimized following the indications
in the paragraph before.
Make sure that the current connections are well connected as well as the
C-clamp, to avoid undesirable heating.
Be careful when manipulating the current terminals in the instrument. You
may get high temperatures in the current connections.
Never connect or disconnect the cables during a measurement. If you must
modify any connection, it must be made after you have pressed the Stop
button.
The equipment must be kept dry and clean.
Never use the equipment if you suspect regarding its functionality. The
equipment must to be put out of service (contact your distributor service
department).