5. Installation and insulation tips
(1) Wrong
The gas pipe and the liquid pipe are insulated
together, which reduces the heating or cooling
effects.
(2) Correct
a. Insulate the gas pipe and the liquid pipe
separately.
[ Caution ]
After the gas pipe and the liquid pipe are insulated separately, binding them too tight may damage the insulation
materials already connected. Binding with ties is not recommended.
b. Pipe connectors shall be properly insulated.
[ Caution ]
No gaps shall be left at the place where insulation materials connect.
If the connecting sections of insulation materials are pulled too much, or wrapped too tightly, these sections are likely
to shrink and leave gaps, causing condensation and dripping. Tight wrapping may squeeze out the air in the materials
and reduce the insulation effects. In addition, the adhesive tape tends to age and peel off over time.
There is no need to wrap the concealed sections indoors with a binding tie, otherwise the insulation effect will be
reduced.
No gaps shall
be left here
Unit
32
Outer tape
Liquid pipe
Pipes should not be bound together.
Heat insulation material
Liquid pipe
Installation
Heat insulation material
Gas pipe
Gas pipe