Installation of Drainage Hose
[ Caution ]
Before installation of the condensate pipeline, determine its direction and elevation to avoid intersection with other
pipelines to ensure that the slope is smooth and straight.
The highest point of the drainage pipe should be equipped with a discharge port to ensure the smooth discharge of
condensate water, and the discharge port must face downwards to prevent dirt from entering the pipe.
Do not connect the drainage pipe to the wastewater pipe, sewage pipe, or other pipes that produce corrosive gases or
odors. Otherwise, the IDU (especially the heat exchanger) may be corroded and odor may enter the room, negatively
impacting the heat exchange effects and user experience. The user will assume responsibility for any consequences
resulting from failure to abide by instructions.
After the pipeline connection is completed, a water test and a full water test should be done to check whether the
drainage is smooth and whether the pipeline system leaks.
The air conditioner drainage pipe must be installed separately from other sewage pipes, rainwater pipes and drainage
pipes in the building.
Adverse slope, convex and concave pipes are prohibited, as improper airflow will cause poor drainage.
Drainage hoses need to be evenly wrapped with thermal insulation pipes to prevent condensation.
Please connect the drainage pipes in the following ways. Improper installation of the pipes may result in water leakage
and damage to furniture and property.
All joints of the drainage system must be sealed to prevent water leakage.
1
Install the drainage hose.
① Connect the drainage hose to the water outlet pipe of the IDU.
② Wrap the joint with waterproof tape, cover the exposed drainage hoses with insulation material, and tie them with a
binding tie.
③ Insert the end of the drainage hose outdoors into the drainage pipe.
[ Note ]
The drainage hose is at the outer layer of the IDU drainage pipe. Try to connect the two pipes till the end.
34
Installation
Water outlet
pipe of IDU
Drainage hose from the
accessory package