Input configuration
Establish the configuration of each of the four available inputs
Send "C<n>, <administrator password>, <NC/NO>, <Persistency time>, <Confirmation time>,
<Resolution time>, <phone book>, <Alert message>".
<n>
admin. pass.
<
>
<NC/NO>
Persistency time
<
>
Confirm. time
<
>
Resolution time
<
>
phone book
<
>
Alert message
<
>
Note: The times are defined in minutes, the maximum allowed value is 999 and the minimum is 0.
Example: To configure input 2 with the data: Polarity: NO; Persistency T: 2 min, Confirmation T: 10
min, Resolution T: 30 min, Phone book: 502445748, 505478596, 504787954, Alert message: High
temp. in chamber 3.
Send:
After a few seconds, the alarm responds with the message:
C2 OK
Consult current configuration
Allows knowing the alarm current configuration. Send "GETCONF, <admin password>".
Example:
After a few seconds, the alarm responds with a message per message input:
C1: Displayed input no.
NO: Input polarity NO, normally open, NC normally closed.
2: Indicates persistency time in minutes.
5: Indicates confirmation time in minutes.
60: Indicates resolution time in minutes.
502445...: Indicates the list of telephones that will receive the input alerts.
Open door...: Indicates the input alert message.
Number of the input to be configured.
Administrator password
Defines the input polarity:
Time the input must remain active to send an alert.
Maximum confirmation time, if after this time a confirmation message has not been
received, the alert will be sent to the next telephone on the list.
Maximum incident resolution time, if after this time the incident has not been solved,
the alert message will be sent again.
List of telephones that will receive the alerts of the configured input. They must be
written in order of priority and separated by the # symbol.
Message that will be received if the alarm of the configured input is activated.
C2, 1234, NO, 2, 10, 30, 502445748#
505478596#504787954, High temp. in
cold room 3
GETCONF, 1234
C1, NO, 2, 5, 60,
502445748#,
open door
cold room 1
NO: Normally open.
NC: Normally closed.
Send
C2, NO, 2, 10, 30,
502445748#505478596#
504787954#,
High temp. in cold room 3
20
Send
C3, NC, 2, 5, 15,
502445748#,
door open in
cold room 1