5 Installation
Fig.175
5.5.5
Selecting the location of the outdoor unit in cold and snowy regions
Fig.176
1/ 2
Specifications
Maximum width equal to the width of the outdoor unit.
Height at least 200 mm greater then the average depth of the
covering of snow.
Location as far as possible from the thoroughfare.
156
1. Locate the noise abatement screen as close as possible to the source
of noise whilst allowing for the free circulation of air in the exchanger
on the outdoor unit and maintenance work.
2. Respect the minimum positioning distances of the outdoor unit from
the noise abatement screen.
Wind and snow can significantly reduce the performance of the outdoor
unit. The location of the outdoor unit must meet the following conditions.
3
1. Install the outdoor unit sufficiently high off the ground to allow
condensates to be discharged correctly.
2. Ensure the base meets the following specifications:
Reason
This helps to protect the exchanger from snow and prevent
the formation of ice during the defrosting operation.
The condensates discharge may freeze, causing a potential
hazard (sheet of black ice).
3. If the outdoor temperatures drop below zero, take the necessary
precautions to prevent the risk of freezing in the evacuation pipes.
4. Place the outdoor units beside each other and not on top of each
other to prevent the condensates from the lower unit to freeze.
MW-C000373-1
4
MW-6000252-2
7800871 - v01 - 18112021