Phasak 6000VA Manual De Uso página 61

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

11: Shutdown point for programmable output
Interface
12: Hot standby function enable/disable
Interface
13: Battery voltage adjustment
Interface
Segurança e harmonia
ININTERRUPTA
Setting
Parameter 2: 001.
Set shutdown time for programmable output.
Parameter 3: Shutdown time in minutes.
Setting range is from 0 to 300. When shutdown time arrives, the programmable output
terminal will be cut off. The default value is 30 minutes.
Parameter 2: 002
Set shutdown voltage for programmable output.
Parameter 3: Shutdown voltage in V.
Setting range is from 11.2 to 13.6. If the battery voltage is less than the setting point,
the programmable output will be cut off. The default value is 11.2V.
Setting
Parameter 2: HS.H
Enable or disable Hot standby function. You may choose following two options in
Parameter 3:
YES: Hot standby function is enabled. It means that the current UPS is set to host of
the hot standby function, and it will restart after AC recovery even without battery
connected.
NO: Hot standby function is disabled. The UPS is running at normal mode and can‟t
restart without battery
Setting
Parameter 2: Select "Add" or "Sub" function to adjust battery voltage to real figure.
Parameter 3: the voltage range is from 0V to 5.7V, the default value is 0V.
3. Operations
PH 9360 | PH 9301
Uninterruptable Power Supply
EN
59

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

10000vaPh 9360Ph 9301Ph 9265Ph 9270

Tabla de contenido