PYD Electrobombas SWITCHMATIC 1 Serie Manual De Instalación Y Mantenimiento página 19

Controlador eléctrico

Publicidad

Idiomas disponibles

Idiomas disponibles

OPERATING AND MAINTENANCE MANUAL
SWITCHMATIC SERIES CONTROLLER
11. ADVANCED PROGRAMMING MENU
- Press
+
+
- Use the keys
or
- Press
to validate and move on to the next.
- The sequence of parameters is as follows:
IT
TYPE
www.proindecsa.com / proindecsa@proindecsa.com
for 5 seconds.
to change the values.
SYSTEM REACTION
Allows to select the type of operation as conventional
(nc = normally closed) or inverted (no = normally open)
pressure switch. *see note 3
(Switchmatic 2 only). Allows to select the working
mode: Individual mode(E00), or Master(E01) and
Slave(E02) mode.
(Switchmatic 2 only). Allows to set the offset between
Pstart 1 and Pstart 2 or between Pstop 1 and Pstop 2.
Allows to set a connection delay between 0 and 9
seconds.
Allows to set a time delay between 0 and 9 seconds
after disconnection.
Enables the ART automatic periodic reset system to be
activated (Ar1) or deactivated (Ar0).
Allows to set a minimum working pressure below which
the device would detect a lack of water. It is very useful
in the basic SWITCHMATIC model where there is no
current consumption reading. See Note 2.
Allows you to set the period of time between 5 and 99
seconds below the minimum working pressure that
would cause a low water alarm.
Switchmatic 2 only). Allows to set a % of In(A) above
which the overcurrent alarm is triggered.
Switching from rS0 to rS1 and pressing ENTER resets
the factory settings.
+
+
19
(diagrama C)
DEFFECT