Switching off the appliance
- Hold down for about 5 seconds the water heater power off button
- As soon as the symbols
- The appliance will be in the OFF state and the display shows
the symbols
(fig. 16 pag. 61).
From this point forward the appliance remains inactive.
In the event that there is a possibility that the temperature
in the room could drop below 3°C, empty the water heat-
er of the water by closing the cold water inlet valve and
opening the hot water tap below the water supply network
of the room.
In case of power off for lengthy periods, disconnect the
omni-polar switch outside the water heater and close the
gas valve upstream of the water heater.
To power the appliance, press for about 5 seconds the power
button
.
SERVICE MENU
Having entered the "SERVICE MENU" it is possible to select the
relevant submenu:
- PARAMETERS MENU
- CALIBRATION MENU MANU
- ALARM HYSTORICAL MENU
- INFO MENU
Parameters menu
Having entered the "PARAMETERS MENU" the operating para-
meters of the appliance can be modified.
- Start-up the appliance, press and hold at the same time the but-
tons
and
for 5 seconds, the symbols
- Release the button
- Hold down
and select code
If the code is incorrect or the time set for the operation should ex-
pire, the appliance automatically returns to the standby or operat-
ing state.
- The display shows:
-
(parameters menu activated) (fig. 19 pag. 61)
-
(parameter 02: gas selection NG/LPG)
- Value of parameter 02
- Press
and
to show subsequent parameters
- Select the parameter and press
and
to change the value
- Confirm by pressing
Exit from the menu automatically stops after 5 minutes of
inactivity or by pressing and holding the
til the display shows MENU' flashing, release the button:
the display shows the set temperature value.
start flashing, release the button
start flashing
, confirm by pressing
: the value flashing, use
button un-
Below is a list of editable parameters:
no.
description
Gas type
02
0 = Natural Gas
1 = LPG
DHW off mode;
08
0 = fixed
1 = associated to DHW setpoint
09
Ignition power
10
Ignition curve
Gas type
0 = natural gas (G20)
13
1 = propan (G31)
2 = butan (G30)
3 = not applicable
Domestic hot water modulation
with flow meter
18
0 = modulation without flow
meter
1 = modulation with flow meter
Water heater flow rate
10 = 14Fi AM Blue
26
11 = 17Fi AM Blue
12 = not applicable
13 = not applicable
27
Modulator reactivity
0 = standard water heater
from 1 to 20 = solar water heat-
28
er, delay (in seconds) of ignition
power if requested
Any other additional parameters with respect to the
table above should not be changed for any reason
.
Calibration menu MANU
Pressure adjustments must be carried out by a qualified
technician
The following operations must be performed in sequence
Before calibration check the mains pressure.
To calibrate the gas valve (standard procedure MANU: partial ca-
libration +/- 1,5 mbar):
- Place the electric switch of the system to off
- Remove the casing by unscrewing the fastening screws located
at the bottom of the water heater and detached the casing from
the top
- Remove the cover that closes the service inlet (located on the
shelf - fig. 11 pag. 61) and insert through the hole the silicon
pressure gauge tube
- Loosen by approximately two turns the screw of the pressure
tap downstream of the gas valve and connect the pressure
gauge to it
- Carefully close the casing and place the electric switch of the
system to on
- Press and hold at the same time the buttons
splay shows first the word Ma and then the word to to compose
Manu (fig. 20 pag. 61)
- Open the hot water tap until the burner start
- The display shows
operating at maximum capacity)
- Use
and
until visualize on the pressure gauge the maxi-
mum burner pressure (see data table)
22
range
default
depending
0 - 1
on the
model
0 - 1
0 ... 40
0 - 3
depending
0 - 3
on the
model
0 - 1
depending
10 - 13
on the
model
0 - 1
0
from 1 to 20
and
(indicating that the water heater is
0
40
1
1
0
0
the di-