ELECTRICAL
REQUIREMENT
DO NOT PLUG IN YOUR SPA WITHOUT
FIRST FILLING WITH WATER!
DANGER – RISK OF ELECTRIC
SHOCK
Installations that do not conform to the
following procedures and requirements
may expose users to electric shock.
Non-conforming installations will not
be covered under warranty.
Your electrical outlet must have
been installed by an electrical
contractor and been approved by a
local building electrical inspection
authority.
115V ELECTRICAL
1. Power supply installation must in-
clude a 15 amp dedicated, ground-
ed wall outlet.
2. The outlet should not be shared
with any other appliance. It must
be labeled and easily accessible to
users.
3. DO NOT use extension cords of any
kind this will invalidate your war-
ranty.
4. For your safety, if you are having
an electrician install an electrical
outlet for the spa it should be no
closer than 6 feet (1.8 m) and no
further than 10 feet (3 m) from the
spa. (Reference National Electrical
Code).
Note: If the manufacturer installed GFCI
Cord is damaged, the GFCI Cord must
be replaced by an authorized service
personnel.
230V ELECTRICAL
1. Installations within 5 feet (1.5 m) of any
ELECTRICAL REQUIREMENTS
metal surfaces must ground the metal sur-
faces to the hot tub. Use an 8 AWG solid
copper wire and attach it to the ground-
ing lug on the power pack, located in the
equipment compartment.
2. Only a licensed electrician may install
power to the spa.
3. Power supply installation must include
a suitably rated ground fault circuit
interrupter (GFCI) as required by NEC.
The circuit breaker must be dedicated
and should not be shared with any other
appliances. It must be labeled and easily
accessible to users.
4. The electrical supply for the spa must
include a suitable rated switch or circuit
breaker to open all ungrounded supply
conductors to comply with the National
Electric Code. The disconnecting means
must be readily accessible to the spa's
occupant but installed at least 5 feet (1.5
m) from the spa water.
5. Power supply lines must be hard wired
into the power pack. DO NOT use
extension or plug-type cords of any kind.
The use of a shut-off box near the hot tub
is also recommended. This box provides
a quick and convenient method to shut off
power to the hot tub for emergencies and
maintenance.
6. Supply lines must be properly sized as
per the NEC (National Electric Code). A
ground line must be provided that is as
large as the largest current carrying con-
ductor, but no less than
8 AWG. All wiring must be copper to en-
sure adequate connections. Do not use
aluminum wire.
7. Please open the front cover of the control
box, and follow the instructions and wiring
diagram printed on the backside.
8. CAUTION, 230V POWERED SPAS –
These spas must be hard wired to your
household electrical service box only. Do
not use an extension cord or any other
disconnect able power cord. The use of