It allows to type in an access protection code to the programming of the control unit.
A four-character alphanumeric code can be typed in by using the numbers from 0 to 9 and the letters A-B-C-D-E-F.
The default value is 0000 (four zeros) and shows the absence of a protection code.
While typing in the code, this operation can be cancelled at any moment by pressing keys + and – simultaneously. Once the password is typed in,
it is possible to act on the control unit by entering and exiting the programming mode for around 10 minutes in order to allow adjustments and tests
on functions.
By replacing the 0000 code with any other code, the protection of the control unit is enabled, thus preventing the access to any other menu. If a
protection code is to be typed in, proceed as follows:
- select the Code menu and press OK.
- the code 0000 is shown, also in the case a protection code has been previously typed in.
- the value of the flashing character can be changed with keys + and -.
- press OK to confirm the flashing character, then confirm the following one.
- after typing in the 4 characters, a confirmation message "CONF" appears.
- after a few seconds, the code 0000 appears again
- the previously stored protection code must be reconfirmed in order to avoid any accidental typing in.
If the code corresponds to the previous one, a confirmation message "OK" appears.
The control unit automatically exits the programming phase. To gain access to the Menus again, the stored protection code must be typed in.
IMPORTANT: TAKE NOTE of the protection code and KEEP IT IN A SAFE PLACE for future maintenance operations.
To remove a code from a protected control unit it is necessary to enter into programming with the password and bring the code back to
the 0000 default value.
IF YOU LOOSE THE CODE, PLEASE CONTACT THE AUTHORISED SERVICE CENTER FOR THE TOTAL RESET OF THE CONTROL UNIT.
MENU
Sets the synchronizing number. It is possible to set a numeric value from 0 to 16.
id
If the ID parameter is to 0 the control unit is set as MASTER, all the other values set the door as SLAVE.
Allows a door set as SLAVE to receive local commands.
loc
See paragraph 8.5 "SYNCHRONIZATION OF TWO OPPOSITE SLIDING DOORS"
8.5) SYNCHRONISATION OF TWO OPPOSITE SLIDING DOORS
It is possible to manage a system composed of two sliding doors by using for each CP.B24-D120 the specific optional control unit SIS, which must be
plugged into the appropriate connector as shown in Fig. 21.
Each SIS unit must be connected to the other one by means of 3 wires by 0,5 sq.mm each, as shown in Fig.21.
One of the control unit must be set as MASTER (ID=0) and the other one as SLAVE (ID=1).
All the commands (given by transmitters, push buttons or safety devices) received by the MASTER sliding door are sent to the SLAVE sliding door, which
will replicate instantaneously the behavior of the MASTER.
The logic LOC can be set in two ways:
ON: the SLAVE sliding door can accept a local command and execute an opening/closing maneuver with no effect on the MASTER sliding door.
OFF: the SLAVE sliding door do not accept any local command and so it will replicate exclusively the behavior of the MASTER sliding door.
A SLAVE sliding door with LOC set to ON can be useful in case it is occasionally necessary the partial opening of a passage which is usually managed
by two synchronized doors, since that a step by step command (or OPEN/CLOSE) given to the SLAVE will have effect only on this last one, while all the
other commands given to the MASTER will be replicated by the SLAVE.
The connection of the safety devices (photocells, safety edges, etc.) can be done indifferently to the MASTER unit or to the SLAVE.
8.6) TRANSMITTERS REMOTE LEARNING
If an already memorised transmitter is available in the receiver it is possible to carry out remote radio learning (without needing to access the control unit).
IMPORTANT: the procedure must be carried out with door open.The logic REM must be ON.
Proceed as follows:
1 Press the hidden key of the transmitter which is already memorised.
2 Press, within 5s, the key of the corresponding transmitter which is already memorised to associate to the new transmitter. The flashing light will turn on.
3 Press within 10s the hidden key of the new transmitter.
4 Press, within 5s, the key of the new transmitter to associate to the channel chosen at point 2. The flashing light will turn off.
5 The receiver memorised the new transmitter and immediately exits from programming.
Note: function not enabled with TO.GO 2/4 AK
8.7) FUSES
F1 =T4A - General protection fuse
8.8) BACK UP BATTERIES
The CP.B24-D120 control panel is equipped with built-in battery chargers to handle in series two 12V 2.1 Ah DA.BT2 batteries (optional - fig. 19) that
allow the operation of the automation even in the case of temporary absence of mains power supply.
During normal mains operation, the card charges the batteries.
The maximum charge current is 1A, the average charge current is 300mA. (respect the polarity).
Charging time with 2.1Ah mod. DA.BT2 batteries: about 3h.
Number of cycles with charged battery for a 4m/600kg gate: about 20.
8.9) DIAGNOSTICS
SWO
SWC
OPEN
P.P.
/PED CLOSE
PHO
PHC
STOP
BAR
28
8.4.8) PASSWORD (CODE)
8.4.9) SYNCHRONIZATION (BUS)
DL 1: Control panel CP.B24-D120 properly powered - Program operating/Control panel programmed.
To each input is associated a line of the LCD screen which in case of activation it turns on according
to the following diagram.
The N.C. inputs are represented by vertical lines.
The N.O. inputs are represented by horizontal lines.
FUNCTION