Figure 3.4: Motor cable shielding connection with PCSx-01 accessory
3.2.4 Grounding Connections
DANGER!
The inverter shall be connected to a Protective Ground (PE).
Use the minimum ground wiring gauge as indicated in the
206,
Table B.2 on page 207
Connect the inverter grounding connections to a ground bus bar, to a single
ground point, or to a common grounding point (impedance ≤ 10 Ω).
The neutral conductor of the network shall be solidly grounded; however,
this conductor shall not be used to ground the inverter.
It is necessary to use a copper cable with 10 mm
the same wire gauge as specified in
page 207
ground protection to be in accordance with IEC61800-5-1 since the leakage
current is greater than 3.5 mA AC.
3.2.5 Control Connections
The control connections (analog inputs/outputs and digital inputs/outputs), shall be performed
in connector XC1 of the CC700 Control Board. Functions and typical connections are presented
in
Figure 3.5 on page
19.
and
Table B.3 on page
and
Table B.3 on page 208
Installation and Connection
Table B.1 on page
208.
minimum or 2 cables with
2
Table B.1 on page
206,
for connecting the inverter to the
Table B.2 on
CFW700 | 17