Weq CFW700 Serie Manual Del Usuario página 44

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Output
speed
For the operation of the multispeed application, it is necessary to set the parameter P0221 or
P0222 to 7 = SoftPLC.
Definition:
The Function 1 of the Application in the parameters P0266 to P0268 represents the Multispeed
command.
The speed reference selection works according to the table below:
DI6
0 V
0 V
0 V
0 V
24 V
24 V
24 V
24 V
If any digital input is selected for Multispeed, it should be considered as 0 V.
The parameters P1011 to P1018 define the speed reference value when the Multispeed is
operating.
The parameters related to this application are:
P1016
P1015
P1014
P1013
P1012
P1011
DI6
DI5
DI4
Figure 4.6: Operation of the Multispeed Application
Table 4.3: Multispeed Reference
DI5
DI4
0 V
0 V
0 V
24 V
24 V
0 V
24 V
24 V
0 V
0 V
0 V
24 V
24 V
0 V
24 V
24 V
Keypad (HMI) and Basic Programming
P1017
P1018
Accelerating
ramp
Time
24 V
0 V (open)
24 V
0 V (open)
24 V
0 V (open)
Speed Reference
P1011
P1012
P1013
P1014
P1015
P1016
P1017
P1018
CFW700 | 39