First Time Power-Up and Start-Up
Step
Action/Display Indication
11
If necessary, change "P0398 – Motor
„
Service Factaor" parameter. This change
will affect the current and the time of the
motor overload protection operation.
Press the
key to the next parameter.
„
13
If necessary, change "P0401 – Motor
„
Rated Current" parameter. This change
will affect P0156, P0157, P0158 and P0410.
Press the
key to the next parameter.
„
15
If necessary, change "P0403 – Motor
„
Rated Frequency " parameter. This
change will affect P0402.
Press the
key to the next parameter.
„
17
If necessary, change "P0405 – Encoder
„
Pulse Number" according to the encoder
model.
Press the
key to the next parameter.
„
19
If necessary, change "P0408 – Run Self-
„
Tuning" parameter.
Press the
key to the next parameter.
„
Run the self-tuning when running in V V W
„
and vector modes.
48 | CFW700
Step
12
If necessary, change "P0400 – Motor
„
Rated Voltage" parameter. This change
corrects the output voltage by the factor
"x = P0400/P0296".
Press the
„
14
If necessary, change "P0404 – Motor
„
Rated Power" parameter. This change
will affect P0410.
Press the
„
16
If necessary, change "P0402 – Motor
„
Rated Speed". This change will affect
P0122 to P0131, P0133, P0134, P0135,
P0182, P0208, P0288 and P0289.
Press the
„
18
If necessary, change "P0406 – Motor
„
Ventilation" parameter.
Press the
„
The parameters to come after selecting
„
P0406 may vary according to the type of
control set at P0202.
20
Press the BACK /ESC key to end the
„
oriented start-up routine.
Press the BACK/ESC again to go back to
„
the monitoring mode.
Figure 5.1: Oriented Start-up
Action/Display Indication
key to the next parameter.
key to the next parameter.
key to the next parameter.
key to the next parameter.