Control terminals

Data for control connections (printed in bold = Lenze setting)
Terminal
Reference potential
7
Analog input
8
0 ... 10 V (changeable under C34)
Internal DC supply for setpoint potentiometer
9
Internal DC supply for digital inputs
20
Digital input Start/Stop
28
Digital input configurable with CE1
E1
Activate fixed setpoint 1 (JOG1)
Digital input configurable with CE2
E2
Direction of rotation
Digital input configurable with CE3
E3
Activate DC injection brake (DCB)
Relay output (normally-open contact)
K12
configurable with C08
Fault (TRIP)
K14
NOTE
LOW = 0 to +3V, HIGH = +12 to +30V.
Protection against contact
All terminals have basic isolation (single insulating distance)
Protection against contact can only be ensured by additional measures (i.e. double insulation)
STOP!
In the case of a Spinning Motor:
To bring free-wheeling loads such as fans to a rest before starting the drive, use the DC
injection braking function ("Auto-DCB"). Starting a drive into a freewheeling motor creates
a direct short-circuit and may result in damage to the drive.
Confirm motor suitability for use with DC injection braking.
Lenze 13435747 EDBSX03 v17 EN, DE, FR, IT, ES
Installation
input resistance: >50 kΩ
(with current signal: 250 Ω)
+10 V, max. 10 mA
+12 V, max. 20 mA
LOW =
Stop
HIGH =
Run Enable
HIGH =
JOG1 active
LOW =
CW rotation
HIGH =
CCW rotation
HIGH =
DCB active
AC 250 V / 3 A
DC 24 V / 2 A ... 240 V / 0.22 A