tected from adverse weather conditions.
-- Regulators with pressure relief valves should be
installed outside the building.
-- Regulators installed inside should be vented
outside.
-- Local state and national codes apply to regulator
installation. Refer to NFPA 54, National Fuel Gas
Code, and NFPA 58, Standard for Storage and
Handling of Liquified Petroleum Gas.
8. Always use pipe joint compound that is resistant to
liquefied petroleum gas and natural gas.
9. Check all connections for gas leaks using ap-
proved gas leak detectors. Gas leak testing is
performed as follows:
WARNING
Fire and Explosion Hazard
■ Do not use open flame (matches, torches,
candles, etc.) in checking for gas leaks.
■ Use only approved leak detectors.
■ Failure to follow this warning can lead to fires
or explosions.
■ Fires or explosions can lead to property
damage, injury or death.
-- Check all pipe connections, hose connections,
fittings and adapters upstream of the gas control
with approved gas leak detectors.
-- In the event a gas leak is detected, check the
components involved for cleanliness and proper
application of pipe compound before further
tightening.
-- Tighten the gas connections as necessary to
stop the leak.
-- After all connections are checked and any leaks
are stopped, turn on the main burner.
-- Stand clear while the main burner ignites to pre-
vent injury caused from hidden leaks that could
cause flashback.
-- With the main burner in operation, check all con-
nections, hose connections, fittings and joints as
well as the gas control valve inlet and outlet
-- If a leak is detected, check the components
involved for cleanliness in the thread areas and
proper application of pipe compound before further
Oval 80 Radiant Tube Heaters
-- If a leak is detected, check the components involved
for cleanliness in the thread areas and proper ap-
plication of pipe compound before further tightening.
-- Tighten the gas connection as necessary to stop the
leak.
-- If necessary, replace the parts or components
involved if the leak cannot be stopped.
-- Ensure all gas leaks have been identified and
repaired before proceeding.
10. Install a sediment trap at the gas valve inlet to
prevent foreign materials (pipe compound, pipe
chips and scale) from entering the gas valve. Debris
blown into the gas valve may cause that valve to
malfunction resulting in a serious gas leak that could
result in a possible fire or explosion causing loss of
products, building or even life. A properly installed
sediment trap will keep foreign materials from enter-
ing the gas valve and protect the safe functioning of
that important safety component.
11. Any heater connected to a piping system must
have an accessible, approved manual shut off valve
installed within six feet (6 ft.) of the heater it serves.
12. Install the proper size of gas supply line to assure
proper functioning of the heaters. Consult your fuel
gas supplier, or the L.B. White Co., Inc. for proper
line sizing and installation.
13. Light according to instructions on heater or within
Owner's Manual.
14. The heater is designed for L.P. vapor withdrawal or
natural gas only. Do not use this heater in a propane
liquid withdrawal system. Do not permit propane in
liquid form to enter the heater.
15. The corrosive atmosphere present in animal
confinement buildings can cause component
failure or heater malfunction. The heater should be
periodically inspected and cleaned in accordance
with the Maintenance and Cleaning Instructions in
this manual. Make sure that livestock is protected
by a back up alarm system that limits high and low
temperatures and also activates appropriate alarms.
16. Take time to understand how to operate and
maintain the heater using the owner's manual. Make
sure you know how to shut off the gas supply to the
building and to the heater. Contact your gas supplier
if you have any questions.
Owner's Manual • Oval 80
11