7.9
COMBUSTIBLE AIR INLET FOR SEALED-CHAMBER INSTALLATION
EN
Check FEATURES page 98 if the purchased stove has a sealed-chamber. If the stove is endowed with a
sealed-chamber and you want also the whole installation with sealed chamber, please read the following
instructions:
• It is necessary to extract the air for combustion directly from outside.
• Use a tube with minimum Ø60 mm and maximum 2 meters lenght; to connect see the back of the stove.
• During installation step is necessary to verify the minimum distances required for the combustible air inlet
as (for example) an open door or window causes a vortex which could remove the combustible air
necessary to the stove (see the underlying scheme).
• On the external wall it is necessary to install a curve at 90° to protect the combustible air inflow from wind
effects: turn the curve inlet downwards, see Fig. 9 page 62.
• Endow the curve with an external shield grid against birds in such a way that it cannot be obstructed
by any object.
• Caution: check with your local authorities if exists any restrictive regulation regarding the combustible
air inlet: if present, they must be applied. In some countries and/or regions the installation with sealed-
chamber is obligatory: in case of doubt, please follow the most restrictive regulations.
7.10
CHIMNEY FLUE CONNECTION
Your pellet stove works through a fume draught forced by a fan. It is obligatory to check that all pipes are
realized in compliance with the following regulation on material selection: EN 1856-1, EN 1856-2 e UNI/TS
11278. All must be effected by specialized personnel or companies as provided by UNI 10683:2012.
• The connection between the appliance and the chimney flue should be short in order to favor the
62
Fig. 9 - Air inlet for sealed-chamber installation
LEGEND
Fig. 9 page 62
1
≥ 1,5 mt
2
≥ 0,3 mt
3-3
Sectional view
4
Shield grid
5
Curve inlet to turn downwards
CLOE - SQUARE