EtherNet/IP Adapter
Introduction
The built-in EtherNet/IP adapter (slave/server) is implemented in the AC30P and AC30D inverters.
To make use of this feature, firmware version V3.x.x needs to be installed in the inverter. The firmware may be updated by downloading the
F
firmware file from the Parker website (see section Firmware Update in Chapter 4) or installed from the latest version of PDQ. With version
e
V3.x.x firmware installed, the AC30EIPS CoDeSys (PDQ/PDD) device is required.
a
Note: V3.x.x firmware has no AFE support and an application size of 128Kbytes (rather than 192Kbytes).
t
u
Res
The following EtherNet/IP features are implemented:
•
Class 1 and Class 3 connections
•
One input assembly instance of up to 500 bytes
•
One output assembly instance of up to 496 bytes
•
Input mapping of up to 32 inverter parameters
•
Output mapping of up to 32 inverter parameters
•
Unicast or multicast communications
•
Requested Packet Interval (RPI) down to 2ms
•
Explicit access of inverter parameters (read and write)
Identity
The EtherNet/IP adapter has the following identity:
Vendor ID
4 (Parker-Hannifin)
Product Code
306 (Parker AC30 Drive)
AC30 series Variable Speed Drive
A-11
Modbus TCP