Io Configure - Parker AC30 Serie Manual Del Producto

Ocultar thumbs Ver también para AC30 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

D-92
Parameter Reference

IO Configure

Setup::Inputs and Outputs
Parameters::Inputs And Outputs::IO Configure
These parameters are used to configure the input signal processing.
Parameter Name
No.
Anin 01 Type
0001
Analog input 1 is associated with terminal X11.1
The signal processing electronics for analog input 1 supports four input ranges.
Anin 01 Offset
0957
The offset is expressed as a percentage of the hardware range selected by 0001 Anin 01 Type. For example, with the 4..20mA range
an offset of 10% is equivalent to 1.6mA on the input.
The offset is added to the measured value.
Anin 01 Scale
0958
The scale is a simple multiplication factor. The input voltage or current is converted to a percentage value. 0957 Anin 01 Offset is
added and the result is multiplied by 0958 Anin 01 Scale. The result is presented in parameter 0039 Anin 01 Value.
Anin 02 Type
0002
Analog input 2 is associated with terminal X11.2
The signal processing electronics for analog input 2 supports two input ranges.
Path
Setup::Inputs and Outputs::Base IO
Parameters::Inputs And Outputs::IO
Configure
Setup::Inputs and Outputs::Base IO
Parameters::Inputs And Outputs::IO
Configure
Same as PNO 957
Same as PNO 1
Default
Range
0
0:-10..10 V
1:0..10 V
2:0..20 mA
3:4..20 mA
0.00
Min to Max
1.0000
Min to Max
0
0:-10..10 V
1:0..10 V
Units
Writable
ALWAYS
ALWAYS
%
ALWAYS
ALWAYS
AC30 series Variable Speed Drive

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ac30pAc30d

Tabla de contenido