Sequencing - Parker AC30 Serie Manual Del Producto

Ocultar thumbs Ver también para AC30 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Sequencing

Parameters::Motor Control::Sequencing
These parameters allow the user of the AC30V to monitor the status and affect the behaviour of the DS402 drive state machine as described in
detail in Appendix B "Sequencing Logic".
Parameter Name
No.
Local
0591
Local (GKP) of Control and Reference.
Local Power Up Mode
1565
The initial value of
0591
0: AS WHEN POWERED DOWN
1: LOCAL
2: REMOTE
Local Reference
0592
Local Reference from GKP.
App Control Word
0610
Control Word from Application (Terminals).
AC30 series Variable Speed Drive
Path
Parameters::Motor Control::Sequencing
Parameters::Motor Control::Sequencing
Local can be selected by the User using this enumerated parameter.
the state when the Drive was powered down (default)
always powers up with
always powers up with
Parameters::Motor Control::Sequencing
Parameters::Motor Control::Sequencing
Parameter Reference
Default
Range
FALSE
0:AS WHEN POWERED DOWN
0
1:LOCAL
2:REMOTE
0591
Local set to TRUE
Local set to FALSE
0591
0.00
0.00 to 100.00
0000
0:SWITCH ON
1:ENABLE VOLTAGE
2:NOT QUICKSTOP
3:ENABLE OPERATION
7:RESET FAULT
8:EXTERNAL FAULT
12:USE JOG REFERENCE
13:REVERSE DIRECTION
14:AUTO INITIALISE
15:EVENT TRIGGERED OP
D-167
Units
Writable
STOPPED
ALWAYS
%
ALWAYS
ALWAYS

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ac30pAc30d

Tabla de contenido