Outdoor Display
LED1 Flashes 8 Times
Turn the unit on. Check the
exhaust temperature of the
compressor.
No
Does the temperature
exceed 230F shortly after the
compressor starts up?
No
Check exhaust temp sensor
resistance. Is it correct?
No
The sensor is faulty,
replace the sensor
Indoor Display
E7
1. Check that the wiring
connections are securely
fastened
2. Check whether the LN wires
are reverse connected
No
Check the outdoor PCB LED
LED
ON/OFF
ON/OFF
ON/OFF
PAGE 36
Overheat Protection for Discharge Temperature
Yes
Yes
Yes
Communication Fault Between Indoor and Outdoor Units
Yes
LED 1
LED 2
OFF
ON
ON
ON
OFF
OFF
ERROR CODES & PROBLEM SOLVING
The power supply is unstable.
There is loss of refrigerant
Check refrigerant charge
The outdoor PCB is faulty, replace
the PCB
LED1 Flashes 15 Times
Correct the wiring between the
indoor and outdoor units
Solution
Outdoor PCB fault
This is caused by Outdoor PCB or Indoor PCB fault. Change
one part firstly, it still unsolved, change another one.
This is caused by Outdoor PCB or Power module fault.
Change one part firstly, if still unsolved change another one.
Spare Parts:
Outdoor PCB
Exhaust sensor
Outdoor Display
Spare Parts:
Indoor PCB
Outdoor PCB
Power module