Checking The Socket Protect Component; Checking The Compressor Windings; Checking The Electrical Base Pan Heater; Checking Indoor Unit Components - Haier AW09ES2VHB Manual De Servicio

Ocultar thumbs Ver también para AW09ES2VHB:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

wiring and connections to the PFC Reactor as well as the PFC
Reactor itself. Repair or replace as necessary.
Step 3
Reconnect the wiring to the module board at the conclusion
of the test.

Checking the Socket Protect Component

Step 1
Disconnect the Socket Protect plug from the control
board connector for this test. Failure to do so may provide
inaccurate readings.
Step 2
Using an Ohmmeter, check the resistance value of the Socket
Protect component. The resistance reading should be 0
Ohms. If it is not, replace the component.
Step 3
Re-seat the plug on the connector at the conclusion of the
test.

Checking the Compressor Windings

Step 1
Disconnect wiring from terminals U (black wire), V (white
wire), and W (red wire) of the power module board.
Step 2
Using an Ohmmeter, check the resistance value of the
compressor windings. Measure between wires U (black wire)
and V (white wire), U (black wire) and W (red wire), and V
(white wire), and W (red wire).
The resistance value of the windings should be nearly
balanced. Check the manufacturer reference table for the
compressor winding values. Repair or replace as needed.
Step 3
Reconnect the wiring to the module board at the conclusion
of the test.
NOTE: Component resistance readings shown in this section
are for reference only. Actual resistance values may differ
based on model being tested.
Component readings shown below are based on a model
HSU12VHGL-G indoor unit.
If the test range of resistance between the two terminals of
electrical base pan heater was between 100 and 500ohm,
then the heater is normal.
Test the resistance between the two terminals of the heater.
If it is open or short circuited, the heater is broken.
Testing of the following components requires the use of an
Ohmmeter and Temperature Probe (Temperature probe is
used during sensor testing only).
NOTE: When using the test probes, probe the back or side
contacts of the plug to obtain the reading. Do not try to
probe the connector end of the plug as this may damage the
contacts of the plug.
NOTE: Use respective temperature / sensor chart for sensor
type being tested.
Coil sensor
Ambient sensor
Step 1
Disconnect the sensor plug from the control board for this
test. Failure to do so may provide inaccurate readings.
Step 2
Using a temperature probe, determine the temperature of
the sensor being tested.
Step 3
Using an Ohmmeter, check the resistance value of the sensor.
Step 4
Referring to the temperature / resistance table for the sensor
being checked, verify the resistance value corresponds to the
temperature checked in step 2.
Replace the sensor if the reading is open, shorted, or outside
the specifications of the temperature / resistance table.
Step 5
Re-seat the plug on the connector at the conclusion of the
test.
ERROR CODES & PROBLEM SOLVING

Checking the Electrical Base Pan Heater

Checking Indoor Unit Components

Checking the Indoor Unit Sensors

PAGE 39

Publicidad

Tabla de contenido
loading

Tabla de contenido