Two-Wire Connection to an AquaLink
or TSTAT
Configure the AquaLink RS Control
System
1.
Turn off the power to both the pool/spa control
system and the heat pump unit.
2.
Connect two (2) wires to the AquaLink RS green
10-pin terminals 1 and 2.
3.
Put DIP S2-1 (pin #1 of the 4 position DIP switch)
into the ON position (see Figure 12).
Install the Remote TSTAT
1.
Turn off the power to both the pool/spa control
system and the heat pump unit.
2.
Remove the screws that attach the service/access
panel to the heat pump unit and the cover to the
junction box (See Figure 10).
3.
Run the wires from the pool/spa control system
into the conduit connection labeled "low voltage
connection", located on the lower right hand side
of the heat pump (See Figure 10).
4.
Connect the wiring from the pool/spa control
system to the heat pump remote control terminal
(See Figure 11b).
5.
Restore power to the heat pump and the pool/spa
control system.
Configure the Control Panel
1.
Make sure the control is in the OFF mode.
2.
To enter the Service Setup mode, press and hold
the MENU, POOL, and SPA buttons for 5
seconds.
NOTE The display will revert back to OFF after one
minute since the last key press.
Figure 11a.
Remote Pool-Off-Spa Connection
(3-Wire Connection)
|
Jandy
®
JE Heat Pumps
Installation and Operation Manual
3.
Press the Up or Down button to display
®
RS
REMOTE. The SELECT REMOTE OFF
(default remote) appears, use the Up or Down
button to scroll through the Remote options. When
you reach REMOTE TSTAT, press the MENU
button to select the remote. Press POOL or SPA
to exit the Service Setup mode.
4.
Press SPA. For heating, adjust the setpoint to the
maximum setting. For chilling, adjust the setpoint
to the minimum setting.
RS485 (4 wire) Connection to AquaLink
1.
Confirm the Jandy JE heat pump and AquaLink
RS software revisions are compatible.
Jandy JE Heat Pump
Power Interface Software
3.0 or Later
NOTE Only a revision "N", or higher, program chip in
2.
Turn off the power to both the heat pump and
the RS control and open the RS Power Center
enclosure and remove the front dead panel.
3.
Remove the two (2) screws holding the bezel in
place and turn the bezel over to view the circuit
board on the back.
4.
Locate the programmed chip on the Power Center
Board. In the center of the chip is the revision
letter. If the revision letter is "
step 5. If the revision level is "
replace the board or connect as shown in Section
4.5
Figure 11b.
AquaLink
Rev.
N or Later
the RS system will support the
pump interface.
AquaLink RS or Remote TSTAT
Connection (2-Wire Connection)
RS
®
®
RS Software
Revision
Jandy JE
heat
" or higher go to
N
" or lower,
MMM