12. TROUBLESHOOTING

12.1 The humidifi er won't start
Possible cause
No power supply
The motor start capacitor has blown

12.2 Air comes out of the distributor, but not atomised water

Possible cause
No water reaches the tank
The cone with fan is clogged
12.3 The humidifi er continuously drains water
Possible cause
The drain siphon is dirty
The unit is installed incorrectly
Less than 30 s have elapsed between stopping
the humidifi er and staring again, not allowing the
siphon to completely drain the water
30
Solution
Check the electrical connections from the control
panel to the terminal block in the humidifi er.
Replace the capacitor with a similar part.
Solution
Check that the water supply is open. Check that the
fi lter on the solenoid valve is not blocked, that the
hoses are not choked or detached. Finally, check
that the fl oat inside the tank is free to move.
Clean the cone with fan from any impurities that
may have formed inside.
Solution
When dirt forms inside the drain siphon, this may be
primed during operation. Remove the drain siphon
and clean (see: par. 6.2 Inspecting and cleaning the
drain siphon)
Check that the unit is installed as described in par.
2.3
Turn the humidifi er off and wait at least 30 s to allow
the siphon to completely drain the water
humiDisk - +030222022 - rel. 2.1 - 01.03.2012
Tab. 12.a
Tab. 12.b
Tab. 12.c