Operating Instructions & Parts Manual
Installation
(Continued)
Leaking joints or couplings will allow air
to leak into the pipe and cause abnormal
pump operation. Make sure to use pipe
joint compound on all male pipe threads.
DUG WELL, CISTERN, LAKE AND
SPRING INSTALLATION (FIGURE 17)
•
Install a foot valve on inlet pipe and
lower into water.
The foot valve
should be at least 18 in.
from the bottom of the well or sand or sediment
could be drawn into the system.
NOTE: When a lake is used as a water
supply, make sure the inlet pipe is deep
enough to be submerged at all times.
Protect the pipe from damage from
swimmers and boats.
Slope the horizontal piping upward
toward the pump to prevent trapping air.
The pipe must be removed during winter
months or protected against freezing.
Protect the pipe from damage from
swimmers and boats.
Install a screen
around the inlet pipe to
prevent the entrapment of swimmers.
DEEP WELL INSTALLATION
DRILLED WELL (4 IN. OR LARGER) WITH
TWO PIPE JET (FIGURES 17 AND 4)
1. Assemble a 1-1/4 in. foot valve (not
included) to the jet body. A 1-1/4 in.
coupling is required to connect the
larger pipe to the jet assembly.
2. Connect the 1 in. pipe threads into the
smaller opening in the jet body.
3. Lower the jet into the well. Add pipe
as needed. Be sure to use pipe joint
compound on all male threads.
4. Position the jet 10 - 20 feet below
the lowest anticipated water level,
but never closer than 5 feet from the
bottom of the well, if possible.
5. Install a well seal to support the pipe
and prevent surface water and other
contaminants from entering the well.
6. Install the horizontal pipe from the well
to the pump. Piping from the vertical
well pipe to the pump should never be
smaller than the well pipes.
7. Slope both pipes upward toward
the pump to prevent trapping air. If
the horizontal distance exceeds 25
feet, see Chart 2 (on page 5) for the
recommended pipe sizes.
www.blueangelpumps.com
Pump
Pump Model
Opening
Deep Well
Inlet:
Suction
Inlet: Drive
Outlet
1-1/4 in. Pipe
1 in.
Pipe
Figure 4 - Two Pipe Jet
DUG WELL, CISTERN, LAKE AND
SPRING WITH TWO PIPE JET (FIGURE
17)
1. Install a 1-1/4 in. foot valve (not
included) to the jet body. A 1-1/4 in.
coupling is required to connect the
larger pipe to the jet assembly.
2. Connect the 1 in. pipe threads into the
smaller opening in the jet body.
3. Lower the jet into the water below
the lowest anticipated water level,
but never closer than 18 in. from the
bottom. Sand or debris may be drawn
into the system if the jet is too close to
the bottom.
4. Provide protection for the jet and
pipes against damage from boats
or swimmers if a lake is used for the
water supply.
Install a screen
around the inlet pipe to
prevent the entrapment of swimmers.
5. Slope the horizontal pipes upward
toward the pump to prevent trapping
air. If horizontal distance exceeds 25
feet, see Chart 2 for recommended
pipe sizes.
DRILLED WELL (2 IN.) WITH SINGLE
PIPE PACKER (FIGURES 17 AND 5)
NOTE: Single pipe packer jets rely on the
space between single pipe and inside of
well casing for return water to operate jet.
Two inch installations must use 1-1/4 in.
galvanized steel pipe with special turned
couplings (1-13/16 in. O.D.) to avoid
restricting flow of return water back to jet.
1. Assemble the foot valve and packer to
the jet body.
2. Lubricate the rubber cups with
4
CHART 2 - PIPE SIZING
Horizontal Distance
0-25
1-1/4 in.
1 in.
3/4 in.
petroleum jelly.
Jet Body
3. Attach the first section of pipe and
lower jet into well.
4. Add pipe until the jet is positioned 5 -
15 feet below the lowest anticipated
Foot Valve
water level. The jet should never be
closer than 5 feet from the bottom of
the well or sand and sediment may be
drawn into the system.
5. With the jet in position, fill the pipes
with water to make sure the rubber
1-1/4 in. Pipe
Figure 5 - Single Pipe Jet
cups are sealed against inside of the
well casing. It may be necessary to
move the jet up and down to seat the
cups.
6. Install the casing adapter and the
horizontal pipes.
7. Slope both pipes upward toward the
pump to eliminate trapping air. If the
horizontal distance exceeds 25 feet,
see Chart 2 for the recommended pipe
sizes.
DEEP WELL PUMP WITH HORIZONTAL
AND VERTICAL STORAGE TANK
(FIGURES 6 AND 7)
1. Install the air volume control on the
tank as shown.
2. Connect the copper tube from the
air volume control to the 1/8 in. NPT
opening directly above the 1-1/4 in.
opening on the front of the pump.
3. Install a valve and isolating hose
between the system and the house
plumbing to aid in pump removal
for servicing and for reducing noise
transmitted through the house piping.
4. Provide a hose bib (faucet) at the
lowest point in the system to drain for
service or storage.
50CJW and 100CJW
(Feet)
26-100
1-1/2 in.
1-1/4 in.
1 in.
Foot Valve
Packer
Cups