5.2
Technical data
Max. flow rate
Max. delivery head
Speed
Mains voltage
Frequency
Nominal current
Energy Efficiency Index (EEI) see name plate
Insulation class
Protection class
Power consumption P
Nominal diameters
Connection flanges
Pump weight
Permissible
ambient temperature
Permissible
fluid temperature
Temperature class
Max. rel. humidity
Degree of pollution
Max. permissible
operating pressure
Approved fluids
Siriux/Siriux-D/Siriux-O
Installation and operating instructions Siriux/Siriux-D/Siriux-O
Depends on the pump type, see catalogue
Depends on the pump type, see catalogue
Depends on the pump type, see catalogue
1~230 V ±10% as per DIN IEC 60038
50/60 Hz
see name plate
see name plate
see name plate
see name plate
1
see type key
see type key
Depends on the pump type, see catalogue
-10°C bis +40°C
For heating, ventilation and air-conditioning applications:
-10°C to +110°C
For drinking water circulation applications:
up to 3.57 mmol/l (25°e): 0°C to +80°C
(max. 60°C according french Norm)
TF110
≤ 95%
2 (IEC 60664-1)
1)
PN 6/10
2)
PN 16
Heating water (as per VDI 2035/VdTÜV Tch 1466)
Water/glycol mixtures, max. mixing ratio of 1:1
(the delivery data of the pump should be corrected accord-
ing to the higher viscosity, depending on the mixing ratio
percentage, if glycol is added.) Only use brand-name goods
with corrosion protection inhibitors; comply with the man-
ufacturer's specifications and safety data sheets.
The pump manufacturer's approval must be obtained for
the use of other fluids.
Ethylene/propylene glycol with corrosion inhibitors.
No oxygen binders, no chemical sealants (pay attention to
system sealed with regard to corrosion technology accord-
ing to VDI 2035; leaks must be reworked)
Commercially available corrosion inhibitors
without anodic inhibitors with a corrosive effect (e.g.
under-dosing due to consumption)
Commercially available combination products
without inorganic or polymer film formers
Commercially available cooling brines
3)
3)
3)
English