Beretta CIAO e 24 C.S.I. Manual De Instalacion Y Uso página 10

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 27
ENGLISH
Long period switching off
In case of absence for long periods of time, set the mode selector
(3 - fi g. 1a) to
(OFF).
Then, close the gas tap present on the system. In this case, anti-
frost device is deactivated: empty the systems, in case of risk of
frost.
4A CONTROLS
At the beginning of the heating season, and occasionally during
use, make sure the hydrometer-thermohydrometer indicates cold
system pressure values between 0.6 and 1.5 bar: this avoids sys-
tem noise levels due to the presence of air. In case of insuffi cient
water circulation, the boiler will switch off. Under no circumstances,
water pressure must be below 0.5 bar (red fi eld).
If this condition is checked, it is necessary to restore water pres-
sure in the boiler proceeding as follows:
- set the mode selector (3 - fi g.1a) to
- turn on the fi lling tap (L fi g. 13) until the pressure value is be-
tween 1 and 1.5 bar.
Carefully close the tap. Replace the mode selector on the initial
position. If pressure drop is frequent, contact the Technical Assis-
tance Service.
5A LIGHT SIGNALS AND FAULTS
The operating status of the boiler is shown on the digital display,
below is a list of the types of displays.
BOILER STATUS
Stand-by
OFF status
ACF module lockout alarm
ACF electrical fault alarm
Limit thermostat alarm
Air pressure switch alarm (C.S.I. models)
Fumes thermostat (C.A.I. models)
H2O pressure switch alarm
NTC domestic water fault
NTC heating fault
Parasite fl ame
Electric calibration min and max heating
Transient awaiting ignition
Air pressure switch intervention (C.S.I. models)
Fumes thermostat intervention (C.A.I. models)
H2O pressure switch intervention
External probe present
Domestic water heat request
Heating heat request
Anti-freeze heat request
Flame present
To restore operation (deactivate alarms):
Faults A 01-02-03
Position the function selector to
set it to the required position
mode). If the reset attempts do not reactivate the boiler, contact the
Technical Assistance Centre.
Fault A 04
In addition to the fault code, the digital display shows the symbol
Check the pressure value indicated by the water gauge:
if it is less than 0.3 bar, position the function selector to
and adjust the fi lling tap (L fi g. 13) until the pressure reaches a
value between 1 and 1.5 bar.
Then position the mode selector to the desired position
10
(OFF)
DISPLAY
-
OFF
A01
A01
A02
A03
A04
A06
A07
A11
ADJ
88
°C
fl ashing
fl ashing
fl ashing
60
°C
80
°C
(OFF), wait 5-6 seconds then
(summer mode) or
(winter
(OFF)
mer) or
(winter).
If pressure drops are frequent, request the intervention of the
Technical Assistance Service.
Fault A 06
The boiler operates normally but cannot reliably maintain a con-
stant domestic hot water temperature, which remains set at around
50°C. Contact the Technical Assistance Centre.
Fault A 07
Contact the Technical Assistance Centre.
.
(sum-

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ciao e 28 c.s.i.Ciao e 24 c.a.i.Ciao e 28 c.a.i.Ciao e serie

Tabla de contenido