PROBLEMS
Problèmes
Diagnostics
The fan does
power supply or
Switch / circuit breaker open
not start and the
regulator screen
Power supply wiring fault
is off
Regulator out of order
Faults present on the regulator
Le ventilateur ne
démarre pas et
l'écran du variateur
est allumé
The motor wiring is defective
Automatic start is not activated
The protective circuit breaker detects a
The fans starts
leakage current and opens
then stops (from
a few seconds to
Faults appear on the regulator
several days)
The fans wheel turns backwards
The fan is in
operation but does
not regulate itself
Faults appear on the regulator
correctly
The fan does not manage to produce the
requested pressure
The instruction value is set incorrectly
The rotation frequency is fixed
at 50 Hz (Fire mode activated)
The casing internal pressure
measurement does not work correctly
Solutions
- Check the presence of the network voltage
- Check that the protective circuit breaker is closed
- Check the power supply wiring in the building up to the
casing switch
- check the power supply wiring in the casing between the
switch and the regulator
- Identify and correct the fault that caused the regulator
to fail
- Change the regulator
- Analyse the fault codes and correct
- Reset the regulator faults
and cut / restart the power supply
- Check the wiring between the regulator and the motor
and cut / restart the power supply
- Check the bridge between the terminals LI1 and +24V (applicable
to regulators ATV12 and ATV312). Cut off the power and restart
- Check compatibility between protection I and max consumed I
- Check that the differential is 300 mA min
- Analyse the fault codes and correct
- Reset the regulator faults and cut / restart the power supply
- Swap 2 phases (U,V,W) on the wire between the regulator
and the motor
- Analyse the fault codes and correct if necessary
- Reset the regulator faults
- The fan is at the end of the curve, curve, the flow rate is
greater than what the fan can supply
- See operating pressure regulation diagram p.10
- On the green connectors: check the wiring between
terminal 6 and terminal 14
- Check that the temperature switch is closed
and cut / restart the power supply
- Check the pressure measurement tube between the pres-
sure switch and the inside of the casing
- Check that the pressure tube is connected to output P2 of
the pressure switch
- Verify operation using an external pressure switch and
compare the value we measured with the operating
pressure set point (see operating pressure regulation
diagram, p.10).
14

ERROR MESSAGES

GB
Regulator fault code
ATV 12
ATV 312
OCF
bLF
SCF + chiffre
SCF
InFE
PHF ; USF
PHF ; USF
OSF
OSF
InF b ; OHF
OHF
OLF
OLF
SOF ; OLF
SOF ; OLF
LFFI
tnF ; OPF1 ; OPF2 tnF
After discovering the cause of the error message, we recommend that an error reset be made (see below).
Should you encounter any problems, please consult our after-sales service, indicating the serial number
of the casing indicated on the manufacturer's plate..
Reset following errors
Meaning
Possible causes
- Current too high in the motor cable or short circuit.
Current too high
- Unsuitable motor or unexpected mechanical problem
Earth fault
Insulation fault in the cables or motor
Internal operating fault
System fault
- Reset the fault and restart
- Power supply voltage too low
Voltage too low
- (Short) network outage
Voltage too high
- Ambient temperature too high
Internal regulator overheat
- Regulator cooling fault
Motor blocked
Check the motor
- The regulator has detected the motor overheating –
Motor overheating
check the motor load
Non-compliant signal from
Check the pressure switch sensor and the wiring
the pressure switch sensor
Maximum number of restarts
on overheat fault reached
- Check the wiring from the motor to the regulator
Motor power supply fault
- Check the condition of the motor wiring
1- Press the Stop/Reset button
2- cLr: confirm acquittal
of a fault
15