TECHNICAL DATA
MODEL
TYP
OUTPUT
(1)
FUEL
- net calorific value
- absolute density
- max. delivery
- pressure at max. delivery
OPERATION
STANDARD APPLICATIONS
AMBIENT TEMPERATUR
COMBUSTION AIR TEMPERATURE
ELECTRICAL SUPPLY
ELECTRIC MOTOR
Running current
Start-up current
IGNITION TRANSFORMER
ELECTRICAL POWER CONSUMPTION
ELECTRICAL PROTECTION
IN CONFORMITY WITH EEC DIRECTIVES
NOISE LEVELS
(2)
APPROVAL
(1) Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m a.s.l.
(2) Pressure at test point 17)(A)p.3, with zero pressure in the combustion chambre, with open gas ring 2)(B)p.7 an maximum burner output
(3) Sound pressure measured in manufacturers combustion laboratory, with burner operating on test boiler and at maximum rated output.
GAS CATEGORY
COUNTRY
IT - AT - GR - DK - FI - SE
ES - GB - IE - PT
NL
FR
DE
BE
LU
ACCESSORIES (optional):
•
KIT FOR LPG OPERATION: The kit allows the RS 190 burners to operate on LPG.
BURNER
OUTPUT
CODE
•
VIBRATION REDUCTION KIT: cod. 3010375
•
GROUND FAULT INTERRUPTER: code 3010329
•
STATUS (see page 20): code 3010322
•
GAS TRAIN ACCORDING TO REGULATION EN 676 (with valves, pressure governor and filter): see page 8.
Important:
The installer is responsible for the addition of any safety device not forseen in the present manual.
2nd stage
Mcal/h
min. 1st stage
Mcal/h
kWh/Nm
Mcal/Nm
kg/Nm
Nm
mbar
°C max 60
V1 - V2
I1 - I2
W max
dBA
CATEGORY
II
2H3B / P
II
2H3P
II
2L3B / P
II
2Er3P
II
2ELL3B /P
I
I
2E(R)B,
3P
II
2E 3B/P
RS 190
kW
465 ... 2290
3010166
RS 190
835 T1
kW
1279 - 2290
1100 - 1970
kW
470
405
NATURAL GAS: G20 - G21 - G22 - G23 - G25
G20
G25
3
10
8.6
3
8.6
7.4
3
0.71
0.78
3
230
267
/h
15
22
• On-Off (1 stop min each 24 hours).
• Two-stage (high and low flame) and single stage (all - nothing)
Boilers: water, steam, diathermic oil
°C
0 - 40
V
230 - 400 with neutral ~ +/-10%
Hz
50 - three-phaes
rpm
2800
W
4500
V
220/240 - 380/415
A
15.8 - 9.1
A
126 - 72.8
230 V - 1 x 8 kV
1 A - 20 mA
5500
IP 44
90/396 - 89/336 - 73/23
83.1
CE
0085AT0042
2