HT HP30D1 Manual De Instrucciones página 2

Publicidad

Idiomas disponibles

Idiomas disponibles

© Copyright HT ITALIA 2012
USER MANUAL
This note must be read in full. Any operations on live conductors can be dangerous
The operator is expected to be fully aware of all necessary electrical safety regulations and procedures. Safe
operation is this responsibility
Never exceed the limit of voltage (600V) or current (1000A AC/DC) indicate in this manual
When measuring current, if strong current nears to the clamp jaw, it will affect the accuracy
While measuring current, always put the tested conductor in the center of clamp jaw so as to obtain a more
accurate reading
It is up to the user to ensure that the equipment is at all times in its original safe conditions
Strong vibrations and impacts may cause damage to the instrument
INSTRUMENT DESCRIPTION
Fig. 1: Instrument description
TECHNICAL SPECIFICATIONS (ambient temperature 18°C ± 5°C and condutctor centered in the torus)
Primary rates current:
Measuring range:
Output ratio:
Accuracy:
Position cable sensitivity:
Temperature Coefficient:
Load impedance:
Frequency range:
MEASUREMENT PROCEDURE
1. Connect clamp's output terminal to the inputs of the instrument to be used as indicator
2. Press and hold the ON/OFF selector on "Test" position for 10s and verify the red LED on. Replace the battery (see Fig. 2) if the
red LED is off. In the event that the LED is turned on for less than 10s are not guaranteed 72 hours of operation
3. Power on the meter by move the selector on "On" position. The red LED should be fixed on. Verify the zero at display of
instrument to be used as indicator. If no move ZERO regulation trimmer on clamp before start the measurement
4. Open the clamp and put the tested conductor in the center of the clamp jaws. No gap is allowed between the connections of
clamp jaws. Always consider the correct connection of clamp (see Fig. 1)
5. Read the current value in the indicator's display. Turn off the meter at the end of measurements
CAUTION: this symbol indicates that equipment and its accessories shall be subject to a separate
collection and correct disposal
ENGLISH
LEGEND:
1.
Arrow which shows
the
reference direction
2.
ZERO
adjustment
thumbwheel
3.
Red LED indicator
4.
ON/OFF
battery test selector
5.
Indicate the limits of
safe
area
handling the clamp
1000A AC/DC FS
10A ÷ 1000A
1000/1
1mV =1A
±(10%rdg+ 2mV) from 10 to 100A
±(2%rdg + 2mV) from 100 to 700A
±(1.5%rdg + 2mV) from 700 to 1000A
0,5% at 50Hz
0.1% of reading / 1°C
>10kΩ e <100pF
DC ÷ 1000Hz
SAFETY WARNING
current
and
for
Fig. 2: Battery replacement operation
Consider the herewith steps to replace internal battery (for
voltage <6V) (see Fig. 2):
1.
Perform a little pressure on the hole on the top of battery
cover by using e.g. a small screwdriver
2.
Shift and detach the battery cover
3.
Remove the battery and replace with a same type new one
considering the correct polarity which is shown on clamp
handle
4.
Replace with a click the battery cover
Pollution degree:
Insulation:
Overvoltage category:
Power supply:
Battery life:
Protection index::
Temperature range:
Max diameter of cable (mm): 83 (bars 100x64 or 122x54)
Dimensioni (mm):
Weight:
Output connector:
Release 1.01 - 27/03/2012
BATTERY REPLACEMENT
2 comply with IEC/EN61010-1
Double insulation
CAT III 600V
1 x 9V battery type 6LR61
about 72 hours
IP20
-5°C ÷ +50°C
336(L) x 137(La) x 42(H)
Ca 1.8kg
Hypertac connector
HP30D1
2