CHAPTER 6
MAINTENANCE
DANGER - ELECTRIC SHOCK RISK
Before any intervention on the system, disconnect the electrical mains. Ensure that the electrical power supply cannot be
restored inadvertently.
DANGER
Refer to the "safety instructions"
• In normal conditions, the pumps do not
require any scheduled maintenance.
• With a view to prevention of
possible faults, it is recommended
to periodically check the pressure
delivered and current absorption. A
reduction in pressure is symptomatic
of pump wear. An increase in current
absorption is symptomatic of abnormal
mechanical friction in the pump.
CHAPTER 7
QUICK TROUBLESHOOTING GUIDE
DANGER
Refer to the "safety instructions".
The pump does not work
• No power supply = turn on the
switch and check that no electrical
connections are loose or defective.
• Check the mains voltage
• Fuse blown = check that the cables and
relative connections are not defective
and replace the fuse if necessary
• The single phase motor thermal cutout
has tripped = this is reset automatically
once the motor has cooled
The pump stops after a short interval of operation due to a tripped motor protection device or electronic control device
• Excessive current absorption = check
the operating condition of the pump
• If foreign bodies are present, blocking
hydraulics = clean the hydraulic
components
20
• Special maintenance may be required
to clean the pump and replace any
worn parts.
• If the pump is not used for prolonged
periods (e.g. for an entire season) it
should be drained completely rinsed
with clean water and stored in a dry
location.
• Motor overload cutout has tripped
= check that the cables and relative
connections are not defective,
check that the pump is not blocked
mechanically, or whether the pump
winding is damaged (replace if
necessary)
• Electrical power line damaged =
replace
• The single phase motor thermal cutout
has tripped = this is reset automatically
once the motor has cooled; check
installation conditions
• Thermal cutout protection setting or
fuses not suitable = check protection
devices with respect to rated current
of pump
• If the pump is used for applications
with drinking water for human
consumption and it is not used for a
long period, repeat the procedures
listed in Installation chapter.
• Pump blocked mechanically = clean
• Control device faulty = replace
• Control device blocked due to tripped
protection = remove causes and press
the Restart button
• Power cable damaged = replace
component
• Motor damaged = replace component
• The pump does not restart = excessive
height of water column above
electronic device (Figure 6)

Publicidad

loading